2020-03-06 12:13:47PLAN REVIEW - MECHANICAL PERMIT # 20021075
  
 CODES IN EFFECT:
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER - BUILDING - PX3169
 PLANS EXAMINER - 1&2 FAMILY - SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 1ST REVIEW
  
 RESULTS: DENIED
  
 YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED
 BELOW.
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 PERMIT REQUIRED FOR WORK OF PREVIOUS OWNER W/O PERMIT
 PER R BROWN
  
 CLASSIFICATION OF WORK SHALL BE ALTERATION LEVEL II
  
 IN ADDITION TO CODES IN EFFECT REFERENCED ABOVE -
 GOVERNING CODES SHALL INCLUDE FBC EXISTING BUILDING
 CHAPT. 8
  
 1. PROVIDE CODE COMPLIANT MECHANICAL PLAN.
  
 FBC 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
 CONSTRUCTION DOCUMENTS SHALL BE DIMENSIONED AND DRAWN
 UPON SUITABLE MATERIAL. CONSTRUCTION DOCUMENTS SHALL BE
 OF SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE
 AND EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT
 IT WILL CONFORM TO THE PROVISIONS OF THIS CODE AND
 RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS
 DETERMINED BY THE BUILDING OFFICIAL.
 EQUIPMENT SCHEDULE ON PLAN SHALL MATCH EQUIPMENT ON
 MANUAL J.
  
 2. PROVIDE ENERGY SUBMITTAL.
 PROVIDE ENERGY GUAGE AND MANUAL J.
  
 FBCE-101.5.1.1.2 SIMULATED PERFORMANCE ALTERNATIVE.+
 AN ACCURATELY COMPLETED RESIDENTIAL BUILDING FORM R405
 (GENERATED BY COMMISSION APPROVED SOFTWARE) SHALL BE
 SUBMITTED TO THE BUILDING OFFICIAL TO DEMONSTRATE CODE
 COMPLIANCE BY SECTION 405.
  
 3. BATHROOM EXHAUST
 M1507.4LOCAL EXHAUST RATES.
 LOCAL EXHAUST SYSTEMS SHALL BE DESIGNED TO HAVE THE
 CAPACITY TO EXHAUST THE MINIMUM AIR FLOW RATE
 DETERMINED IN ACCORDANCE WITH TABLE M1507.4.
  
 BATHROOMS-TOILET ROOMS - MECHANICAL EXHAUST CAPACITY OF
 50 CFM INTERMITTENT OR 20 CFM CONTINUOUS
  
 4. M1411.3 CONDENSATE DISPOSAL.
 CONDENSATE FROM COOLING COILS AND EVAPORATORS SHALL BE
 CONVEYED FROM THE DRAIN PAN OUTLET TO AN APPROVED PLACE
 OF DISPOSAL. SUCH PIPING SHALL MAINTAIN A MINIMUM
 HORIZONTAL SLOPE IN THE DIRECTION OF DISCHARGE OF NOT
 LESS THAN 1/8 UNIT VERTICAL IN 12 UNITS HORIZONTAL
 (1-PERCENT SLOPE). CONDENSATE SHALL NOT DISCHARGE INTO
 A STREET, ALLEY OR OTHER AREAS WHERE IT WOULD CAUSE A
 NUISANCE.
  
 5. M1602.3BALANCED RETURN AIR.
  
 6. E3901.12 HVAC OUTLET.
  
 7. M1411.8 LOCKING ACCESS PORT CAPS.
  
 8. M1307.2ANCHORAGE OF APPLIANCES.
 THIS DETAIL SHOULD BE SIGNED AND SEALED BY AN ENGINEER
  
 9. THE CONTRACTOR OR DESIGNER OF RECORD SHALL PROVIDE A
 TITLE BLOCK AND SIGNATURE ON THE MECHANICAL PLAN SHEET
 - SECTION 107.2.1 WPB. IF THE DESIGNER IS A FL.
 LICENSED ARCHITECT OR ENGINEER, HE/SHE SHALL ALSO
 PROVIDE AN ORIGINAL SEAL AND WET SIGNATURE PER FL.
 STATUE AND SECTIONS 61G15-16.003 AND 23.002 FAC.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
  
  
  
  
  
  