| 2020-03-06 12:13:47 | PLAN REVIEW - MECHANICAL PERMIT # 20021075 |
| | |
| | CODES IN EFFECT: |
| | 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST |
| | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, |
| | CHAPTER 1 ADMINISTRATION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| | FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| | 6TH EDITION |
| | |
| | CHRISTOPHER S. THROOP, C.B.O. |
| | PLANS EXAMINER - BUILDING - PX3169 |
| | PLANS EXAMINER - 1&2 FAMILY - SFP306 |
| | CONSTRUCTION SERVICES DIVISION |
| | TEL: 561-805-6726 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | 1ST REVIEW |
| | |
| | RESULTS: DENIED |
| | |
| | YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED |
| | BELOW. |
| | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT |
| | |
| | PERMIT REQUIRED FOR WORK OF PREVIOUS OWNER W/O PERMIT |
| | PER R BROWN |
| | |
| | CLASSIFICATION OF WORK SHALL BE ALTERATION LEVEL II |
| | |
| | IN ADDITION TO CODES IN EFFECT REFERENCED ABOVE - |
| | GOVERNING CODES SHALL INCLUDE FBC EXISTING BUILDING |
| | CHAPT. 8 |
| | |
| | 1. PROVIDE CODE COMPLIANT MECHANICAL PLAN. |
| | |
| | FBC 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | CONSTRUCTION DOCUMENTS SHALL BE DIMENSIONED AND DRAWN |
| | UPON SUITABLE MATERIAL. CONSTRUCTION DOCUMENTS SHALL BE |
| | OF SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE |
| | AND EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT |
| | IT WILL CONFORM TO THE PROVISIONS OF THIS CODE AND |
| | RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS |
| | DETERMINED BY THE BUILDING OFFICIAL. |
| | EQUIPMENT SCHEDULE ON PLAN SHALL MATCH EQUIPMENT ON |
| | MANUAL J. |
| | |
| | 2. PROVIDE ENERGY SUBMITTAL. |
| | PROVIDE ENERGY GUAGE AND MANUAL J. |
| | |
| | FBCE-101.5.1.1.2 SIMULATED PERFORMANCE ALTERNATIVE.+ |
| | AN ACCURATELY COMPLETED RESIDENTIAL BUILDING FORM R405 |
| | (GENERATED BY COMMISSION APPROVED SOFTWARE) SHALL BE |
| | SUBMITTED TO THE BUILDING OFFICIAL TO DEMONSTRATE CODE |
| | COMPLIANCE BY SECTION 405. |
| | |
| | 3. BATHROOM EXHAUST |
| | M1507.4LOCAL EXHAUST RATES. |
| | LOCAL EXHAUST SYSTEMS SHALL BE DESIGNED TO HAVE THE |
| | CAPACITY TO EXHAUST THE MINIMUM AIR FLOW RATE |
| | DETERMINED IN ACCORDANCE WITH TABLE M1507.4. |
| | |
| | BATHROOMS-TOILET ROOMS - MECHANICAL EXHAUST CAPACITY OF |
| | 50 CFM INTERMITTENT OR 20 CFM CONTINUOUS |
| | |
| | 4. M1411.3 CONDENSATE DISPOSAL. |
| | CONDENSATE FROM COOLING COILS AND EVAPORATORS SHALL BE |
| | CONVEYED FROM THE DRAIN PAN OUTLET TO AN APPROVED PLACE |
| | OF DISPOSAL. SUCH PIPING SHALL MAINTAIN A MINIMUM |
| | HORIZONTAL SLOPE IN THE DIRECTION OF DISCHARGE OF NOT |
| | LESS THAN 1/8 UNIT VERTICAL IN 12 UNITS HORIZONTAL |
| | (1-PERCENT SLOPE). CONDENSATE SHALL NOT DISCHARGE INTO |
| | A STREET, ALLEY OR OTHER AREAS WHERE IT WOULD CAUSE A |
| | NUISANCE. |
| | |
| | 5. M1602.3BALANCED RETURN AIR. |
| | |
| | 6. E3901.12 HVAC OUTLET. |
| | |
| | 7. M1411.8 LOCKING ACCESS PORT CAPS. |
| | |
| | 8. M1307.2ANCHORAGE OF APPLIANCES. |
| | THIS DETAIL SHOULD BE SIGNED AND SEALED BY AN ENGINEER |
| | |
| | 9. THE CONTRACTOR OR DESIGNER OF RECORD SHALL PROVIDE A |
| | TITLE BLOCK AND SIGNATURE ON THE MECHANICAL PLAN SHEET |
| | - SECTION 107.2.1 WPB. IF THE DESIGNER IS A FL. |
| | LICENSED ARCHITECT OR ENGINEER, HE/SHE SHALL ALSO |
| | PROVIDE AN ORIGINAL SEAL AND WET SIGNATURE PER FL. |
| | STATUE AND SECTIONS 61G15-16.003 AND 23.002 FAC. |
| | |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | |
| | |
| | |
| | |
| | |
| | |
| | |