| 2020-03-06 12:15:04 | PLAN REVIEW - ELECTRICAL |
| | |
| | CODES IN EFFECT: |
| | 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST |
| | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, |
| | CHAPTER 1 ADMINISTRATION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| | FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| | 6TH EDITION |
| | |
| | CHRISTOPHER S. THROOP, C.B.O. |
| | BUILDING PLANS EXAMINER, PX3169 |
| | 1&2 FAMILY PLANS EXAMINER, SFP306 |
| | CONSTRUCTION SERVICES DIVISION |
| | TEL: 561-805-6726 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | 1ST REVIEW |
| | |
| | RESULTS: DENIED |
| | |
| | YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED |
| | BELOW. |
| | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT |
| | |
| | PERMIT REQUIRED FOR WORK OF PREVIOUS OWNER W/O PERMIT |
| | PER R BROWN |
| | |
| | CLASSIFICATION OF WORK SHALL BE ALTERATION LEVEL II |
| | |
| | GOVERNING CODES SHALL INCLUDE FBC EXISTING BUILDING |
| | CHAPT. 8 |
| | |
| | 1. PROVIDE A CODE COMPLIANT ELECTRICAL PLAN. |
| | |
| | PERMITS |
| | 105.1 REQUIRED. |
| | |
| | 2. PROVIDE FLOOR PLAN. |
| | FBC 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | CONSTRUCTION DOCUMENTS SHALL BE DIMENSIONED AND DRAWN |
| | UPON SUITABLE MATERIAL. CONSTRUCTION DOCUMENTS SHALL BE |
| | OF SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE |
| | AND EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT |
| | IT WILL CONFORM TO THE PROVISIONS OF THIS CODE AND |
| | RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS |
| | DETERMINED BY THE BUILDING OFFICIAL. |
| | |
| | 3. PROVIDE RISER DIAGRAHM. |
| | |
| | RISER: |
| | PROVIDE RISER DIAGRAM, SHOWING ALL DETAILS OF SERVICE |
| | EQUIPMENT, UNDERGROUND OR OVERHEAD SERVICE, WIRE AND |
| | BREAKER SIZES FOR SERVICE AND FEED TO ANY SUB-PANEL(S). |
| | |
| | 4. PROVIDE LOAD CALCULATIONS. |
| | |
| | PROVIDE ACCURATE LOAD CALCULATION INCLUDING ALL LOADS. |
| | NEC 220; FBC RE E3602.2 |
| | PROVIDE LOAD CALCULATION FOR SERVICE, INCLUDE EXISTING |
| | AND NEW LOADS TO CONFIRM CAPACITY OF SERVICE IS |
| | ADEQUATE. NEC 215.2, 220, 408.30; FBC RE E3602.2 |
| | |
| | 5. PROVIDE PANEL SCHEDULE. |
| | |
| | PROVIDE PANEL SCHEDULE INDICATING ANY NEW OR ALTERED |
| | CIRCUITS, THE WIRE AND BREAKER SIZE FOR THESE CIRCUITS, |
| | AND AFCI OR GFCI PROTECTION WHERE APPLICABLE TO COMPLY |
| | WITH CODE. NEC 210.8, 210.12, 210.19, 210.20, 215.5, |
| | 408.4; WPB FBC 107.3.5; FBC RE E3706.2, E3902. |
| | |
| | 6. THE CONTRACTOR OR DESIGNER OF RECORD SHALL PROVIDE A |
| | TITLE BLOCK AND SIGNATURE ON THE MECHANICAL PLAN SHEET |
| | - SECTION 107.2.1 WPB. IF THE DESIGNER IS A FL. |
| | LICENSED ARCHITECT OR ENGINEER, HE/SHE SHALL ALSO |
| | PROVIDE AN ORIGINAL SEAL AND WET SIGNATURE PER FL. |
| | STATUE AND SECTIONS 61G15-16.003 AND 23.002 FAC. |
| | |
| | |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |