| 2020-03-25 13:30:22 | RE-ROOF SECOND BUILDING REVIEW COMMENTS |
| | CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS. |
| | |
| | 1- OK |
| | |
| | 2- DECK REPAIR ENGINEERING CALCULATIONS SUBMITTED; |
| | A) OK. |
| | |
| | B) ENGINEER TO PROVIDE SKETCH SHOWING AREAS WHERE |
| | REPAIRS ARE REQUIRED. SEC. 107.2.1 CITY AMENDMENTS. |
| | |
| | RESPONSE: |
| | REPEAT COMMENT. NOT ADDRESSED. NOTE: BECAUSE OF THE |
| | CURRENT CORONAVIRUS EVENT, HIS CAN BE DONE VIA E-MAIL. |
| | |
| | 3- STRUCTURAL DECK REPAIRS REQUIRE A SEPARATE PERMIT. |
| | THIS CAN BE DONE AS A SUB-PERMIT TO THE ROOFING PERMIT. |
| | NEED A SEPARATE PERMIT APPLICATION FOR THIS SCOPE OF |
| | WORK. NOTE: THIS WORK CAN NOT BE DONE BY THE ROOFING |
| | CONTRACTOR UNLESS ROOFING CONTRACTOR POSSESSES THE |
| | PROPER LICENSE TO PERFORM THIS STRUCTURAL WORK. |
| | |
| | RESPONSE: |
| | REPEAT COMMENT. PERMIT APPLICATION FOR THE STRUCTURAL |
| | REPAIRS WAS NOT SUBMITTED. |
| | |
| | 4- PROVIDE COMPLETE FLAT ROOF FLORIDA PRODUCT APPROVAL. |
| | PRODUCT APPROVAL SUBMITTED IS MISSING THE FLORIDA |
| | PRODUCT APPROVAL COVER PAGE. THIS PAGE IS REQUIRED |
| | BECAUSE IT SHOWS THE CURRENT CODE VERSION AND THE |
| | PRODUCT APPROVAL STATUS. CHAPTER 553 F.S. AND FAC |
| | 61G20-3.001. |
| | |
| | RESPONSE: |
| | REPEAT COMMENT. NOT ADDRESSED. NOTE: BECAUSE OF THE |
| | CURRENT CORONAVIRUS EVENT, HIS CAN BE DONE VIA E-MAIL. |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & |
| | REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| | NECESSARY. (NOTE: SUBMIT OLD PERMIT PACKAGE FOR |
| | REFERENCE). A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |
| | PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY |
| | QUESTIONS REGARDING THESE COMMENTS, |
| | JULIO GOMEZ |
| | COMMERCIAL COMBINATION PLANS EXAMINER |
| | DEVELOPMENT SERVICES DEPARTMENT |
| | BUILDING DIVISION |
| | (561)805-6712 |
| | [email protected] |
| | |