| 2020-02-25 14:32:10 | RE-ROOF BUILDING REVIEW COMMENTS |
| | CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS. |
| | |
| | NOTE: SEC. 702.6 FBC-EXISTING BUILDING. ALL NEW WORK |
| | SHALL COMPLY WITH THE MATERIALS AND METHODS |
| | REQUIREMENTS IN THE FLORIDA BUILDING CODE. |
| | |
| | 1- NEED A FIELD UPLIFT RESISTANCE TEST (TAS 124) AS |
| | REQUIRED BY LIMITATION #8 ON PAGE 5 OF 6 OF FLORIDA |
| | PRODUCT APPROVAL FL16758-R14 SUBMITTED. |
| | SEC. 107.2.1 CITY AMENDMENTS. |
| | |
| | 2- DECK REPAIR ENGINEERING CALCULATIONS SUBMITTED; |
| | A) CALCULATIONS SUBMITTED HAVE A COPY OF A DIGITAL |
| | SIGNATURE. THIS IS NOT A DIGITAL SUBMITTAL. |
| | CALCULATIONS NEED TO HAVE THE ORIGINAL SEAL AND |
| | SIGNATURE OF THE ENGINEER OF RECORD AS REQUIRED BY SEC. |
| | 61G15-23.003 FAC AND CHAPTER 471 F.S. WHEN SUBMITTING |
| | PLANS/DOCUMENTS FOR PUBLIC RECORDS. |
| | NOTE: THIS APPLIES TO OTHER CALCULATION SUBMITTED BY |
| | THE SAME ENGINEER (ROOF WIND PRESSURE & ATTACHMENT |
| | DESIGN, AND ROOF STORM WATER DRAINS CALCULATIONS). |
| | |
| | B) ENGINEER TO PROVIDE SKETCH SHOWING AREAS WHERE |
| | REPAIR ARE REQUIRED. SEC. 107.2.1 CITY AMENDMENTS. |
| | |
| | 3- STRUCTURAL DECK REPAIRS REQUIRE A SEPARATE PERMIT. |
| | THIS CAN BE DONE AS A SUB-PERMIT TO THE ROOFING PERMIT. |
| | NEED A SEPARATE PERMIT APPLICATION FOR THIS SCOPE OF |
| | WORK. NOTE: THIS WORK CAN NOT BE DONE BY THE ROOFING |
| | CONTRACTOR UNLESS ROOFING CONTRACTOR POSSESSES THE |
| | PROPER LICENSE TO PERFORM THIS STRUCTURAL WORK. |
| | |
| | 4- PROVIDE COMPLETE FLAT ROOF FLORIDA PRODUCT APPROVAL. |
| | PRODUCT APPROVAL SUBMITTED IS MISSING THE FLORIDA |
| | PRODUCT APPROVAL COVER PAGE. THIS PAGE IS REQUIRED |
| | BECAUSE IT SHOWS THE CURRENT CODE VERSION AND THE |
| | PRODUCT APPROVAL STATUS. CHAPTER 553 F.S. AND FAC |
| | 61G20-3.001. |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & |
| | REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| | NECESSARY. (NOTE: SUBMIT OLD PERMIT PACKAGE FOR |
| | REFERENCE). A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |
| | PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY |
| | QUESTIONS REGARDING THESE COMMENTS, |