| Plan Review Notes For Permit 20021055 |
| Permit Number |
20021055 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2020-02-27 15:31:42 | RESIDENTIAL (R3) RE-ROOF BUILDING REVIEW CHECKLIST. | | | CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS. | | | | | | 1- FLAT ROOF NOA 20-0110.11 SUBMITTED: CLEARLY MARK | | | WHICH APPROVED ASSEMBLY IS GOING TO BE INSTALLED TO | | | VERIFY COMPLIANCE WITH THE DESIGN PRESSURES OF SEC. | | | R301.2.1 FBC-RESIDENTIAL. NOTE: IF THE SELECTED | | | ASSEMBLY DOESN'T MEET THE DESIGN PRESSURES FOR ALL ROOF | | | ZONES, THEN SIGNED AND SEALED RAS 117 CALCULATIONS ARE | | | REQUIRED. SEE GENERAL LIMITATION #7 ON LAST PAGE OF | | | NOA. | | | NOTE: ASSEMBLIES THAT ARE LIMITED BY GENERAL LIMITATION | | | #9 MAY NOT BE USED IF THE MAXIMUM DESIGN PRESSURES | | | DON'T MEET THE DESIGN PRESSURES FOR ALL ROOF ZONES. | | | GENERAL LIMITATION #9 DOESN'T ALLOW NAIL ENHANCEMENT. | | | SEE GENERAL LIMITATION #9 ON LAST PAGE OF NOA. | | | | | | | | | PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY | | | QUESTIONS REGARDING THESE COMMENTS, | | | JULIO GOMEZ | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | DEVELOPMENT SERVICES DEPARTMENT | | | BUILDING DIVISION | | | (561)805-6712 | | | [email protected] |
|