| Plan Review Notes For Permit 20021045 |
| Permit Number |
20021045 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2020-02-26 05:40:57 | 1) THE LATICRETE PRODUCT MUST COMPLY WITH FBC-PLUMBING | | | SEC.417.5.2.5. THE PRODUCT SHALL MEET THE REQUIREMENTS | | | OF ANSI A118.10. THE SUBMITTED SPECIFICATIONS DO NOT | | | SHOW COMPLIANCE WITH THIS STANDARD.SUBMIT COMPLETE | | | SPECIFICATIONS THAT SHOW COMPLIANCE. | | | | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | PLUMBING PLAN REVIEW | | | 561-805-6692 | | | [email protected] | | | |
|