| 2020-05-04 10:59:40 | 1) ALL GAS APPLIANCES SHALL BE LISTED AND LABELED PER |
| | FBC-FUEL GAS SEC.301.3. THE SUBMITTED SPECIFICATIONS |
| | FOR THE RANGE, GRILL AND POOL HEATER DO NOT SHOW THE |
| | LISTING FOR THE APPLIANCES. |
| | 2) THE POOL HEATER SHALL HAVE A THERMAL EFFICIENCY OF |
| | 82% PER FBC-ENERGY SEC.R403.10.4. SUBMIT VERIFICATION |
| | OF COMPLIANCE. |
| | 3) SUBMIT COMBUSTION AIR CALCULATIONS FOR THE UNVENTED |
| | GAS LOG, FIREPLACE, CLOTHES DRYERS, AND RANGE, FBC-FUEL |
| | GAS SEC.304.1. THE RESPONSE FROM FAE REFERS TO SHT. |
| | M1.1. THERE WAS NO SHT. M1.1 SUBMITTED. |
| | 4) SUBMIT THE SPECIFICATIONS FOR THE GENERATOR THAT |
| | SHOW THE MODEL OF THE GENERATOR BEING INSTALLED. WPB |
| | AMEND. TO FBC SEC. 107.2.1. |
| | 5) THE FUEL FLOW RATE (BTU LOAD) SHOWN IN THE SUBMITTED |
| | GENERATOR SPECIFICATIONS DOES NOT CORRELATE WITH THE |
| | BTU LOAD OF THE GENERATOR SHOWN ON THE GAS RISER. |
| | CLARIFY. |
| | 6) THE GAS PLANS CALL OUT 2 DIFFERENT GAS SIZING TABLES |
| | FOR THE LOW PRESSURE SYSTEM- 402.4 (1) & 402.4 (2). |
| | CLARIFY. |
| | 7) SHOW THE DISTANCE FROM THE MAIN GAS LINE TO THE |
| | GENERATOR. |
| | 8) SHOW THE DISTANCE FROM EACH REGULATOR TO THE GAS |
| | APPLIANCE. INCLUDE THE DIMENSIONS OF ALL OFFSETS AND |
| | DROPS TO THE APPLIANCE. THE CODE REQUIRES THE DEVELOPED |
| | LENGTH. |
| | 9) THE 1 1/2 INCH SCH. 40 PIPE LINE TO THE POOL HEATER, |
| | FIREPLACE AND FIREPIT IS UNDERSIZED PER GAS SIZING |
| | TABLE 402.4 (2). THE TABLE ALLOWS 532 MBTU'S AT THE |
| | CALCULATED LENGTH AND THE PLANS SHOW 540 MBTU'S. |
| | 10) THE 3/4 INCH SCH. 40 METALLIC PIPE TO THE FIREPIT |
| | IS UNDERSIZED PER GAS SIZING TABLE 402.4 (2). THE TABLE |
| | ALLOWS 92 MBTU'S AT THE CALCULATED LENGTH AND THE PLANS |
| | SHOW 100 MBTU'S. |
| | 11) THE 1 1/4 INCH LINE TO THE GENERATOR MAY BE |
| | UNDERSIZED. THE DISTANCE FROM THE REGULATOR TO THE |
| | GENERATOR IS REQUIRED TO DETERMINE IF THE PIPE SIZE IS |
| | CODE COMPLIANT. |
| | |
| | TIM LARGE |
| | CHIEF PLUMBING INSPECTOR |
| | PLUMBING PLAN REVIEW |