| 2020-02-26 17:30:57 | 1ST GAS REVIEW**DENIED** WITH COMMENTS |
| | |
| | NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS |
| | TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE |
| | GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS. |
| | SOME COMMENT MAY NOT APPLY BUT ARE PROVIDED FOR |
| | REFERENCES. |
| | |
| | |
| | 1. THE PHYSICAL ADDRESS OF THE RESIDENCE MUST BE ON |
| | PLANS IN FULL, NUMBER, STREET, CITY, STATE AND ZIP CODE |
| | PER THE WPB AMENDMENTS TO THE FBC SEC.107.2.1 |
| | INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | |
| | 2. PLEASE PROVIDE FOR EACH AND ALL APPLIANCES |
| | MANUFACTURES SPECIFICATION SHEETS/INSTALLATION MANUAL |
| | FOR EQUIPMENT TO VERIFY COMPLIANCE WITH 2017 FBC FUEL |
| | GAS R 2408.1. |
| | |
| | 3. PLEASE SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE |
| | PRESSURE REGULATORS. REGULATORS INSTALLED ON THE |
| | EXTERIOR OF THE BUILDING SHALL BE APPROVED FOR OUTDOOR |
| | INSTALLATION PER THE 2017 FBC FUEL GAS R 2421.1. |
| | |
| | 4. PLEASE SHOW ALL SHUT-OFF VALVE TO EACH APPLIANCE ON |
| | FLAT AND ISOMETRIC PER THE 2017 FBC FUEL GAS R 2420.4. |
| | |
| | 5. PLEASE SHOW THE DISTANCE FROM THE POINT OF DELIVERY |
| | TO THE MOST REMOTE OUTLET IN THE BUILDING AND/OR SYSTEM |
| | PER THE 2017 FBC FUEL GAS. R 2413.4.1. |
| | |
| | 6. SUBMIT COMBUSTION AIR CALCULATIONS FOR GAS |
| | APPLIANCES. WHERE IS COMBUSTION AIR PROVIDED BY THE |
| | BUILDING'S MECHANICAL VENTILATION SYSTEM, THE SYSTEM |
| | SHALL PROVIDE THE SPECIFIED COMBUSTION AIR RATE IN |
| | ADDITION TO THE REQUIRED VENTILATION AIR? 2017 FBC |
| | FUELS GAS R 2407.9.3. COMBINED COMBUSTION AIR AND |
| | VENTILATION AIR SYSTEM. |
| | |
| | 7. SHUT OFF VALVES FOR FIREPLACE SHALL BE IN EACH ROOM |
| | AS THE UNIT NOT OUTSIDE PLEASE SHOW ON FLAT AND |
| | ISOMETRIC PER THE 2017 FBC FUEL GAS R 2420.5. |
| | |
| | 8. PLEASE SHOW ALL UNIONS IN FRONT OF REGULATOR 1' OF |
| | EITHER SIDE PER THE 2017 FBC FUEL GAS R 2421.2. |
| | |
| | 9. PLEASE LABEL DRIP LEG ON ALL EQUIPMENT INSTALLED PER |
| | THE 2017 FBC FUEL GAS R 2419.2. |
| | |
| | 10. SHOW DIMENSIONS OF THE LOCATION FOR EACH TANKLESS |
| | WATER HEATER NEXT TO EACH OTHER AND DISTANCE OF ANY |
| | OPERABLE DOORS OR WINDOWS IN RELATION TO THE WATER |
| | HEATER. THE LOCATION OF THE WATER HEATER SHALL COMPLY |
| | WITH THE MANUFACTURER'S INSTALLATION INSTRUCTIONS PER |
| | THE WPB AMENDMENTS TO THE FBC SEC. 107.2.1. INFORMATION |
| | ON CONSTRUCTION DOCUMENTS. |
| | |
| | 11. SUBMIT SPECIFICATION FOR THE GENERATOR. THE |
| | MANUFACTURER'S SPECIFICATIONS FOR THE GENERATOR SHALL |
| | BE ONSITE FOR FINAL GAS INSPECTION. THE GENERATOR SHALL |
| | BE LISTED AND APPROVED. NFPA 58 SEC. 5.20.1. THE |
| | GENERATOR SHALL MEET THE REQUIREMENTS OF UL 2200. |
| | |
| | 12. GENERATOR IS NOT SHOWN IN PLANS AND IF IT IS A |
| | FUTURE MUST BE SHOWN LABELED WITH SHUTOFF VALVE AND |
| | HARD CAP PER THE WPB AMENDMENTS TO THE FBC SEC.107.2.1 |
| | INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & |
| | REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION, MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |
| | LUIS A. CRESPO |
| | PLUMBING INSPECTOR / |
| | PLUMBING PLAN REVIEW |
| | AVAILABLE FROM 6:30 AM 7:30 / 2:00 PM TO 5:00 PM |
| | [email protected] |
| | 561-805-6720 |
| | |