Plan Review Notes
Plan Review Notes For Permit 20021036
Permit Number 20021036
Review Stop G
Sequence Number 1
Notes
Date Text
2020-02-26 17:30:571ST GAS REVIEW**DENIED** WITH COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
 SOME COMMENT MAY NOT APPLY BUT ARE PROVIDED FOR
 REFERENCES.
  
  
 1. THE PHYSICAL ADDRESS OF THE RESIDENCE MUST BE ON
 PLANS IN FULL, NUMBER, STREET, CITY, STATE AND ZIP CODE
 PER THE WPB AMENDMENTS TO THE FBC SEC.107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 2. PLEASE PROVIDE FOR EACH AND ALL APPLIANCES
 MANUFACTURES SPECIFICATION SHEETS/INSTALLATION MANUAL
 FOR EQUIPMENT TO VERIFY COMPLIANCE WITH 2017 FBC FUEL
 GAS R 2408.1.
  
 3. PLEASE SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE
 PRESSURE REGULATORS. REGULATORS INSTALLED ON THE
 EXTERIOR OF THE BUILDING SHALL BE APPROVED FOR OUTDOOR
 INSTALLATION PER THE 2017 FBC FUEL GAS R 2421.1.
  
 4. PLEASE SHOW ALL SHUT-OFF VALVE TO EACH APPLIANCE ON
 FLAT AND ISOMETRIC PER THE 2017 FBC FUEL GAS R 2420.4.
  
 5. PLEASE SHOW THE DISTANCE FROM THE POINT OF DELIVERY
 TO THE MOST REMOTE OUTLET IN THE BUILDING AND/OR SYSTEM
 PER THE 2017 FBC FUEL GAS. R 2413.4.1.
  
 6. SUBMIT COMBUSTION AIR CALCULATIONS FOR GAS
 APPLIANCES. WHERE IS COMBUSTION AIR PROVIDED BY THE
 BUILDING'S MECHANICAL VENTILATION SYSTEM, THE SYSTEM
 SHALL PROVIDE THE SPECIFIED COMBUSTION AIR RATE IN
 ADDITION TO THE REQUIRED VENTILATION AIR? 2017 FBC
 FUELS GAS R 2407.9.3. COMBINED COMBUSTION AIR AND
 VENTILATION AIR SYSTEM.
  
 7. SHUT OFF VALVES FOR FIREPLACE SHALL BE IN EACH ROOM
 AS THE UNIT NOT OUTSIDE PLEASE SHOW ON FLAT AND
 ISOMETRIC PER THE 2017 FBC FUEL GAS R 2420.5.
  
 8. PLEASE SHOW ALL UNIONS IN FRONT OF REGULATOR 1' OF
 EITHER SIDE PER THE 2017 FBC FUEL GAS R 2421.2.
  
 9. PLEASE LABEL DRIP LEG ON ALL EQUIPMENT INSTALLED PER
 THE 2017 FBC FUEL GAS R 2419.2.
  
 10. SHOW DIMENSIONS OF THE LOCATION FOR EACH TANKLESS
 WATER HEATER NEXT TO EACH OTHER AND DISTANCE OF ANY
 OPERABLE DOORS OR WINDOWS IN RELATION TO THE WATER
 HEATER. THE LOCATION OF THE WATER HEATER SHALL COMPLY
 WITH THE MANUFACTURER'S INSTALLATION INSTRUCTIONS PER
 THE WPB AMENDMENTS TO THE FBC SEC. 107.2.1. INFORMATION
 ON CONSTRUCTION DOCUMENTS.
  
 11. SUBMIT SPECIFICATION FOR THE GENERATOR. THE
 MANUFACTURER'S SPECIFICATIONS FOR THE GENERATOR SHALL
 BE ONSITE FOR FINAL GAS INSPECTION. THE GENERATOR SHALL
 BE LISTED AND APPROVED. NFPA 58 SEC. 5.20.1. THE
 GENERATOR SHALL MEET THE REQUIREMENTS OF UL 2200.
  
 12. GENERATOR IS NOT SHOWN IN PLANS AND IF IT IS A
 FUTURE MUST BE SHOWN LABELED WITH SHUTOFF VALVE AND
 HARD CAP PER THE WPB AMENDMENTS TO THE FBC SEC.107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION, MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 LUIS A. CRESPO
 PLUMBING INSPECTOR /
 PLUMBING PLAN REVIEW
 AVAILABLE FROM 6:30 AM 7:30 / 2:00 PM TO 5:00 PM
 [email protected]
 561-805-6720
  