| 2020-03-05 14:24:25 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| | MARSHAL, WITH THE FOLLOWING COMMENTS: |
| | |
| | |
| | 1) SHEET 1.1 - THERE IS AN INDICATION OF OCCUPANCY AS |
| | GROUP B - BUSINESS. |
| | |
| | WHAT IS THE PROPOSED USE OF THE BUILDING? IT APPEARS TO |
| | BE MERCANTILE PER THE FLORIDA FIRE PREVENTION CODE. |
| | |
| | PLEASE REVIEW AND CORRECT OR PROVIDE DETAILS. |
| | |
| | |
| | 2) SHEET 1.1 - THE ARE NO INDICATIONS OF ELECTICAL |
| | SHEETS NOR ELECTRICAL WORK |
| | |
| | PLEASE REVIEW AND CORRECT. |
| | |
| | |
| | 3) SHEET 3.0 - THERE IS NO INDICATIONS OF AN OCCUPANCY |
| | LOAD PER # 1 ABOVE. |
| | |
| | PER NFPA 101, CH 7 |
| | |
| | 7.3 CAPACITY OF MEANS OF EGRESS. |
| | 7.3.1 OCCUPANT LOAD. |
| | 7.3.1.1 SUFFICIENT CAPACITY. |
| | 7.3.1.1.1 THE TOTAL CAPACITY OF THE MEANS OF EGRESS FOR |
| | ANY STORY, |
| | BALCONY, TIER, OR OTHER OCCUPIED SPACE SHALL BE |
| | SUFFICIENT FOR THE |
| | OCCUPANT LOAD THEREOF. |
| | 7.3.1.1.2 FOR OTHER THAN EXISTING MEANS OF EGRESS, |
| | WHERE MORE |
| | THAN ONE MEANS OF EGRESS IS REQUIRED, THE MEANS OF |
| | EGRESS SHALL BE |
| | OF SUCH WIDTH AND CAPACITY THAT THE LOSS OF ANY ONE |
| | MEANS OF |
| | EGRESS LEAVES AVAILABLE NOT LESS THAN 50 PERCENT OF THE |
| | REQUIRED |
| | CAPACITY. |
| | 7.3.1.2* OCCUPANT LOAD FACTOR. THE OCCUPANT LOAD IN ANY |
| | BUILDING OR PORTION THEREOF SHALL BE NOT LESS THAN THE |
| | NUMBER OF |
| | PERSONS DETERMINED BY DIVIDING THE FLOOR AREA ASSIGNED |
| | TO THAT USE |
| | BY THE OCCUPANT LOAD FACTOR FOR THAT USE AS SPECIFIED |
| | IN TABLE |
| | 7.3.1.2, FIGURE 7.3.1.2 (A), AND FIGURE 7.3.1.2(B). |
| | WHERE BOTH |
| | GROSS AND NET AREA FIGURES ARE GIVEN FOR THE SAME |
| | OCCUPANCY, |
| | CALCULATIONS SHALL BE MADE BY APPLYING THE GROSS AREA |
| | FIGURE TO THE |
| | GROSS AREA OF THE PORTION OF THE BUILDING DEVOTED TO |
| | THE USE FOR |
| | WHICH THE GROSS AREA FIGURE IS SPECIFIED AND BY |
| | APPLYING THE NET |
| | AREA FIGURE TO THE NET AREA OF THE PORTION OF THE |
| | BUILDING DEVOTED TO |
| | THE USE FOR WHICH THE NET AREA FIGURE IS SPECIFIED. |
| | |
| | PROVIDE THE SIZE OF EGRESS WIDTH AND THE OCCUPANCY LOAD |
| | COUNT THROUGH THOSE EXITS. |
| | |
| | PLEASE REVIEW AND PROVIDE. |
| | |
| | |
| | |
| | 4) SHEET 3.0 - THERE IS NO INDICATIONS OF THE |
| | SEPARATION OF THE REQUIRED EGRESSES. |
| | |
| | 7.5.1.3.1 WHERE MORE THAN ONE EXIT, EXIT ACCESS, OR |
| | EXIT DISCHARGE IS |
| | REQUIRED FROM A BUILDING OR PORTION THEREOF, SUCH |
| | EXITS, EXIT ACCESSES, |
| | OR EXIT DISCHARGES SHALL BE REMOTELY LOCATED FROM EACH |
| | OTHER AND BE |
| | ARRANGED TO MINIMIZE THE POSSIBILITY THAT MORE THAN ONE |
| | HAS THE |
| | POTENTIAL TO BE BLOCKED BY ANY ONE FIRE OR OTHER |
| | EMERGENCY |
| | CONDITION. |
| | 7.5.1.3.2* WHERE TWO EXITS, EXIT ACCESSES, OR EXIT |
| | DISCHARGES ARE |
| | REQUIRED, THEY SHALL BE LOCATED AT A DISTANCE FROM ONE |
| | ANOTHER NOT |
| | LESS THAN ONE-HALF THE LENGTH OF THE MAXIMUM OVERALL |
| | DIAGONAL |
| | DIMENSION OF THE BUILDING OR AREA TO BE SERVED, |
| | MEASURED IN A |
| | STRAIGHT LINE BETWEEN THE NEAREST EDGE OF THE EXITS, |
| | EXIT ACCESSES, OR |
| | EXIT DISCHARGES, UNLESS OTHERWISE PROVIDED IN 7.5.1.3.3 |
| | THROUGH |
| | 7.5.1.3.5. |
| | |
| | PER # 1 ABOVE, PLEASE PROVIDE THE DIMENSION OF THE |
| | SEPARATION OF EGRESS |
| | |
| | |
| | |
| | 5) SHEET 3.0 - THERE IS NO CLEAR EXIT SIGANGE WITH |
| | ILLUMINATION. |
| | |
| | 7.10 MARKING OF MEANS OF EGRESS. |
| | 7.10.1 GENERAL. |
| | 7.10.1.1 WHERE REQUIRED. MEANS OF EGRESS SHALL BE |
| | MARKED IN |
| | ACCORDANCE WITH SECTION 7.10 WHERE REQUIRED IN CHAPTERS |
| | 11 |
| | THROUGH 43. |
| | 7.10.1.2 EXITS. |
| | 7.10.1.2.1* EXITS, OTHER THAN MAIN EXTERIOR EXIT DOORS |
| | THAT OBVIOUSLY |
| | AND CLEARLY ARE IDENTIFIABLE AS EXITS, SHALL BE MARKED |
| | BY AN APPROVED |
| | SIGN THAT IS READILY VISIBLE FROM ANY DIRECTION OF EXIT |
| | ACCESS. |
| | 7.10.1.2.2* HORIZONTAL COMPONENTS OF THE EGRESS PATH |
| | WITHIN AN EXIT |
| | ENCLOSURE SHALL BE MARKED BY APPROVED EXIT OR |
| | DIRECTIONAL EXIT SIGNS |
| | WHERE THE CONTINUATION OF THE EGRESS PATH IS NOT |
| | OBVIOUS. |
| | |
| | PLEASE REVIEW AND PROVIDE. |
| | |
| | |
| | |
| | 6) SHEET 3.0 - THERE IS NO INDICATION OF EGRESS |
| | LIGHTING |
| | |
| | 7.8 ILLUMINATION OF MEANS OF EGRESS. |
| | 7.8.1 GENERAL. |
| | 7.8.1.1* ILLUMINATION OF MEANS OF EGRESS SHALL BE |
| | PROVIDED IN |
| | ACCORDANCE WITH SECTION 7.8 FOR EVERY BUILDING AND |
| | STRUCTURE WHERE |
| | REQUIRED IN CHAPTERS 11 THROUGH 43. FOR THE PURPOSES OF |
| | THIS |
| | REQUIREMENT, EXIT ACCESS SHALL INCLUDE ONLY DESIGNATED |
| | STAIRS, AISLES, |
| | CORRIDORS, RAMPS, ESCALATORS, AND PASSAGEWAYS LEADING |
| | TO AN EXIT. FOR THE |
| | PURPOSES OF THIS REQUIREMENT, EXIT DISCHARGE SHALL |
| | INCLUDE ONLY |
| | DESIGNATED STAIRS, AISLES, CORRIDORS, RAMPS, |
| | ESCALATORS, WALKWAYS, AND EXIT |
| | PASSAGEWAYS LEADING TO A PUBLIC WAY. |
| | 7.8.1.2 ILLUMINATION OF MEANS OF EGRESS SHALL BE |
| | CONTINUOUS DURING THE |
| | TIME THAT THE CONDITIONS OF OCCUPANCY REQUIRE THAT THE |
| | MEANS OF EGRESS |
| | BE AVAILABLE FOR USE, UNLESS OTHERWISE PROVIDED IN |
| | 7.8.1.2.2. |
| | 7.8.1.2.1 ARTIFICIAL LIGHTING SHALL BE EMPLOYED AT SUCH |
| | LOCATIONS AND FOR |
| | SUCH PERIODS OF TIME AS ARE NECESSARY TO MAINTAIN THE |
| | ILLUMINATION TO THE |
| | MINIMUM CRITERIA VALUES HEREIN SPECIFIED. |
| | |
| | PLEASE REVIEW AND PROVIDE. |
| | |
| | |
| | |
| | 7) SHEET 3.0 - PER THE APPLICABLE OCCUPANCY CHAPTER |
| | EMERGENCY LIGHTING IS NOT INDICATED. |
| | |
| | 7.9 EMERGENCY LIGHTING. |
| | 7.9.1 GENERAL. |
| | 7.9.1.1* EMERGENCY LIGHTING FACILITIES FOR MEANS OF |
| | EGRESS SHALL BE |
| | PROVIDED IN ACCORDANCE WITH SECTION 7.9 FOR THE |
| | FOLLOWING: |
| | (1) BUILDINGS OR STRUCTURES WHERE REQUIRED IN CHAPTERS |
| | 11 THROUGH 43 |
| | (2) UNDERGROUND AND LIMITED ACCESS STRUCTURES AS |
| | ADDRESSED IN SECTION |
| | 11.7 |
| | (3) HIGH-RISE BUILDINGS AS REQUIRED BY OTHER SECTIONS |
| | OF THIS CODE |
| | (4) DOORS EQUIPPED WITH DELAYED-EGRESS LOCKS |
| | (5) STAIR SHAFTS AND VESTIBULES OF SMOKEPROOF |
| | ENCLOSURES, FOR WHICH THE |
| | FOLLOWING ALSO APPLY: |
| | (A) THE STAIR SHAFT AND VESTIBULE SHALL BE PERMITTED TO |
| | INCLUDE A |
| | STANDBY GENERATOR THAT IS INSTALLED FOR THE SMOKEPROOF |
| | ENCLOSURE MECHANICAL VENTILATION EQUIPMENT. |
| | (B) THE STANDBY GENERATOR SHALL BE PERMITTED TO BE USED |
| | FOR THE |
| | STAIR SHAFT AND VESTIBULE EMERGENCY LIGHTING POWER |
| | SUPPLY. |
| | (6) NEW ACCESS-CONTROLLED EGRESS DOORS IN ACCORDANCE |
| | WITH 7.2.1.6.2 |
| | |
| | PLEASE REVIEW AND PROVIDE. |
| | |
| | |
| | 8) SHEET 3.2 & 10.1 - THE REAR DOOR IS NOT INDICATED ON |
| | THE DOOR SCHEDULE, INCLUDING NO HARDWARE. |
| | |
| | PLEASE REVIEW AND CORRECT. |
| | |
| | IF THIS IS ALSO A REQUIRED EXIT DOOR, (WHICH IT |
| | SHOULDBW) ALL EXIT HARDWARE SHALL BE INCLUDED. |
| | |
| | |
| | |
| | 9) PLEASE SECURE AND BIND ALL APPLICABLE SHEETS INTO 2 |
| | COMPLETE SETS NOT 6 SEPARATE SHEETS. |
| | |
| | |
| | |
| | 10) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET |
| | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE |
| | ABOVE. |
| | |
| | |
| | |
| | 11) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE |
| | RE-SUBMITTAL OF THE ABOVE. |
| | |
| | |
| | |
| | PETER LEDUC |
| | FIRE MARSHAL |
| | 561-804-4709 |
| | [email protected] |
| | |