| 2020-03-03 09:45:35 | 2017 FBC- BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 20021029 |
| | ADD: 420 CLAREMORE DR. |
| | CONT: RICHARD MCDONALD CONSTRUCTION CO. INC. |
| | TEL: 561-795-4055 |
| | E-MAIL: [email protected] |
| | |
| | 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION. |
| | |
| | 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW |
| | CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES |
| | SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA |
| | BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: TUES. / MARCH 03/2020 |
| | ACTION: DENIED |
| | |
| | 1) SHEET S-0.0 UNDER THE HEADING FOUNDATIONS NOTE # 8 |
| | STATES TO FOLLOW THE GEOTECHNICAL |
| | REPORT RECOMMENDATIONS AND SITE PREPARATIONS IN ALL |
| | ASPECTS. THERE WAS NO GEO-TECHNICAL REPORT SUBMITTED |
| | FOR THE NEW FOUNDATIONS, HOW TO ACHIEVE 2500 PSF |
| | BEARING VALUE. |
| | |
| | 2017 FBC-B 1803.5.2 QUESTIONABLE SOIL. WHERE THE |
| | CLASSIFICATION, STRENGTH OR COMPRESSIBILITY OF THE SOIL |
| | IS IN DOUBT OR WHERE A LOAD-BEARING VALUE SUPERIOR TO |
| | THAT SPECIFIED IN THIS CODE IS CLAIMED, THE BUILDING |
| | OFFICIAL SHALL BE PERMITTED TO REQUIRE THAT A |
| | GEOTECHNICAL INVESTIGATION BE CONDUCTED. |
| | |
| | 2) SHEET S-1.1 SHOWS IN THE ROOF FRAMING PLAN THE ROOF |
| | RAFTERS TO BE SPACED AT 16 INCHES ON CENTER WHERE AS ON |
| | THE SAME SHEET IN THE ROOF FRAMING NOTES, NOTE # 1 THE |
| | NOTE STATES THAT THE 2 X12 RAFTERS ARE TO BE SPACED AT |
| | 24 INCHES ON CENTER. PLEASE CORRECT THE DISCREPANCY IN |
| | THE PLANS. THE SPAN TABLE, 2017 FBC-B TABLE 2308.7.2(2) |
| | WILL ALLOW THE 2X12 RAFTERS TO SPAN WITH CEILING THE |
| | ALLOWABLE SPAN AT 16 INCHES ON CENTER BUT NOT AT 24 |
| | INCHES ON CENTER. |
| | |
| | 3A) SHEET 10.1 ARCHITECTURAL PLAN HAS THE DOOR SCHEDULE |
| | AND HARDWARE SCHEDULE WHAT IS NOT SHOWN IS PANIC |
| | HARDWARE ON THE NEW EXIT DOORS, SLIDERS AND SWING |
| | DOORS. THE 2017 FBC-B SECTION 1010.1.10 IN AN ASSEMBLY |
| | OCCUPANCY WITH AN OCCUPANT LOAD OF 50 OR MORE. RAG TOPS |
| | IN THE PAST HAS HAD ASSEMBLY OCCUPANCY EVENTS IN THE |
| | PAST. ON THE INTERNET RAGTOPS IS ALSO ADVERTISED AS AN |
| | AUTOMOBILE MUSEUM ALSO CONSIDERED AN ASSEMBLY |
| | OCCUPANCY. THE PLANS STATE A BUSINESS OCCUPANCY. PLEASE |
| | CLARIFY THE USAGE FOR THIS TENANT SPACE, ON THE PLANS, |
| | IT WILL CLARIFY WHAT TYPE OF HARDWARE WOULD BE REQUIRED |
| | DEPENDING ON THE MOST RESTRICTIVE USAGE. NOA- |
| | 18-0221.11. |
| | |
| | 3B) THE SAME HOLDS TRUE FOR THE NEW SWING DOOR BEING |
| | ADDED. WITHIN THE SUBMITTED TECHNICAL SHEET 1-14 THE |
| | PRESSURES VARY DEPENDING ON THE LOCKING MECHANISM, |
| | PLEASE IDENTIFY WHICH LOCKING DEVICES WILL BE USED IN |
| | THIS INSTALLATION. THANK YOU. NOA-17-0426.02. |
| | |
| | 4A) IN THIS SUBMITTAL THERE WAS NO ROOFING PRODUCT |
| | APPROVAL SUBMITTED. SHEET A-3.2 NOTES THE FLORIDA |
| | APPROVAL FL- 11819-R3. ALL OF THE MODELS OF METAL ROOF |
| | ARE TO BE INSTALLED OVER OPEN FRAMING, NOT OVER A |
| | PLYWOOD DECK. PLEASE ALSO SUBMIT THE PRODUCT APPROVAL |
| | FOR THE UNDERLAYMENT TO REVIEW FOR CODE COMPLIANCE. |
| | |
| | 4B) W. P. B. 107.3.4.1 PRODUCT APPROVALS. THOSE |
| | PRODUCTS WHICH ARE REGULATED BY THE DCA RULE 9N-03 |
| | SHALL BE REVIEWED AND APPROVED IN WRITING BY THE |
| | DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR |
| | JURISDICTIONAL APPROVAL. FL 61G1-23.015 (2) THE |
| | ARCHITECT IS RESPONSIBLE FOR SUPERVISING AND REVIEWING |
| | ALL PROJECT DATA, REPORTS, SHOP DRAWINGS ETC.. |
| | |
| | 5) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION |
| | & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |
| | JAMES A. WITMER BN, PX, SFP & CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |