| Plan Review Notes For Permit 20021000 |
| Permit Number |
20021000 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2020-02-28 15:28:17 | SFR REMODEL | | | REVIEWED BY ROGER MCPHERSON | | | 561-805-6716 | | | [email protected] | | | | | | CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107 | | | 1) DRAWING A-1 HAS A DETAIL FOR A LEDGER BOARD DETAIL | | | SHOWING 5/8" LAG BOLTS INTO A STEEL BEAM - LAG BOLTS | | | ARE NOT AN ACCEPTABLE ANCHOR FOR ATTACHMENT TO A STEEL | | | BEAM, PLEASE REVISE DETAIL. PLEASE SHOW THE TYPE LENGTH | | | AND DIAMETER OF THE ANCHOR TO BE USED. | | | 2) PLEASE SHOW THE WIND DESIGN CRITERIA USED - FBC | | | R301.2.1.1 - - - FBC 1603.1.4 | | | 3) PLEASE SHOW THE EXTERIOR DOOR OPENING WIND DESIGN | | | PRESSURE FBC R301.2.1 | | | 4) PLEASE SHOW THE DETAILS FOR THE EXTERIOR WALL | | | INFILL. | | | 5) PLEASE PROVIDE COMPLETE (FRONT PAGES AND | | | INSTALLATION INSTRUCTIONS) MIAMI DADE OR FLORIDA STATE | | | PRODUCT APPROVALS FOR THE NEW EXTERIOR DOOR. |
|