| 2020-04-10 13:19:58 | 2ND REVIEW FBC-2017 MECHANICAL |
| | PERMIT #20020949 |
| | 4/10/20 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| | 2017 |
| | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH |
| | EDITION 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) THE AC CALCULATION SUMMARY SHOWS THE 8.5-TON CARRIER |
| | RTU IS OVER SIZED. THE CALCULATIONS INDICATE 74.1 MBH |
| | TOTAL COOLING AND 57 MBH SENSIBLE COOLING REQUIRED |
| | (APPROX. 6.5 TON), HOWEVER THE RTU-1 SCHEDULE ON THE |
| | PLAN INDICATES 103 MBH TOTAL AND 81 MBH COOLING- |
| | SECTION C403.2.1 FBC EC. |
| | |
| | 2) COMMENT #4 FROM THE 1ST REVIEW HAS NOT BEEN |
| | ADDRESSED ON THE PLAN. 4) M2.1 & M6.1: INDICATE HOW O/A |
| | IS BEING PROVIDED TO THE LARGE CONFERENCE ROOM AND |
| | PROVIDE CALCULATIONS- TABLE 403.3.1.1 FBC M. PLEASE |
| | NOTE THAT AN AUTOMATICALLY CONTROLLED SHUTOFF DAMPER IS |
| | REQUIRED FOR THE REQUIRED O/A INLET OR DUCT TO THE AIR |
| | HANDLER- SECTION C403.2.4.3 FBC EC. |
| | |
| | 3) THE REQUESTED ENGINEERING FOR INSTALLATION OF THE |
| | RTU HAS NOT BEEN PROVIDED. PLEASE NOTE THE ENGINEERING |
| | MAY BE DEFERRED- SECTION 107.3.4.1 WPB. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |