| 2020-03-16 16:33:59 | 1ST REVIEW FBC-2017 MECHANICAL |
| | PERMIT #20020949 |
| | 3/16/20 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| | 2017 |
| | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH |
| | EDITION 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) PROVIDE AC COOLING AND HEATING CALCULATIONS FOR THE |
| | RTU AND THE MINI-SPLIT SYSTEMS- SECTION C403.2.1 FBC |
| | EC. |
| | |
| | 2) M2.1: A DUCT SMOKE DETECTOR IS REQUIRED IN THE |
| | SUPPLY AIR SYSTEM OF THE RTU- SECTION 606.2.1. |
| | |
| | 3) M2.1 & M6.1: PROVIDE AUTOMATICALLY CONTROLLED |
| | SHUTOFF DAMPERS FOR THE RTU O/A INTAKE- SECTION |
| | C403.2.4.3 FBC EC. |
| | |
| | 4) M2.1 & M6.1: INDICATE HOW O/A IS BEING PROVIDED TO |
| | THE LARGE CONFERENCE ROOM AND PROVIDE CALCULATIONS- |
| | TABLE 403.3.1.1 FBC M. PLEASE NOTE THAT AN |
| | AUTOMATICALLY CONTROLLED SHUTOFF DAMPER IS REQUIRED FOR |
| | THE REQUIRED O/A INLET OR DUCT- SECTION C403.2.4.3 FBC |
| | EC. |
| | |
| | 5) PROVIDE A MECHANICAL ROOF PLAN SHOWING THE LOCATIONS |
| | OF THE RTU AND THE CU, AND PROVIDE INSTALLATION |
| | ENGINEERING- SECTION 301.15 FBC M |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD |
| | SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER |
| | SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN |
| | THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS |
| | PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS |
| | PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR |
| | UPDATED. |
| | |