| Date |
Text |
| 2020-05-08 12:56:04 | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| | 6TH ED, CHAPTER 1. |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| | 6TH EDITION |
| | FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017 |
| | 6TH EDITION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE |
| | FS = FLORIDA STATUTES |
| | FAC = FLORIDA ADMINISTRATIVE CODE |
| | |
| | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| | |
| | 1. PROVIDE ACCURATE LOAD CALCULATION FOR PANEL B. |
| | DEMAND FACTORS ARE NOT PERMITTED ON FEEDERS LESS THAN |
| | 100 AMP CAPACITY. NEC 220.82; FBC RE E3602.2.2.1 |
| | 2. BASED ON THE LOAD SPECIFIED FOR PANEL B, WHEN DEMAND |
| | FACTORS ARE NOT USED, THE PANEL AND FEEDERS WOULD BE |
| | OVERLOADED. PROVIDE CORRECTION. NEC 215.2, 220, 408.30; |
| | FBC RE E3704.1, E3706.1 |
| | 3. |
| | 4. |
| | 5. . |
| | 6. |
| | 7. FEED TO INTERIOR PANEL A FROM DISCONNECT A IS |
| | REQUIRED TO HAVE AN EQUIPMENT GROUNDING CONDUCTOR, |
| | SIZED PER CODE. PROVIDE CORRECTION. NEC 250.122; FBC RE |
| | E3704.6, 3607.3.1 |
| | 8. FEED TO PANEL B IS SHOWN WITH ONE # 6 CONDUCTOR. A |
| | NEUTRAL CONDUCTOR AND AN EQUIPMENT GROUNDING CONDUCTOR |
| | IS REQUIRED AT THIS PANEL. PROVIDE CORRECTION. NEC |
| | 250.24(C), 250.122; FBC RE E3704.6, 3607.3.1; WPB FBC |
| | 107.2.1 |
| | 9. |
| | |
| | END OF COMMENTS. |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| | RESUBMITTING, PROVIDE A RESPONSE LETTER ADDRESSING EACH |
| | ITEM ALONG WITH THE CITY RESUBMITTAL FORM. |
| | ADDITIONALLY, INSERT CORRECTED PAGES INTO THE ORIGINAL |
| | SUBMITTAL AND REMOVE THE PREVIOUSLY REVIEWED SHEETS. |
| | ONE COPY OF THE PREVIOUSLY REVIEWED SHEETS SHOULD |
| | REMAIN IN PACKAGE AND BE MARKED OLD SHEETS. |
| | |
| | SINCERELY, |
| | |
| | PHIL PETTY |
| | ELECTRICAL PLANS EXAMINER |
| | 561-805-6742 |
| | [email protected] |
| | |