2020-03-23 18:57:0403/23/2020 PLUMBING 1ST REVIEW **DENIED** WITH COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 1. ON ISOMETRIC (E1.0) DRAWING KITCHEN SINK CANNOT
 DISCHARGE INTO WET VET OF A BATHROOM GROUP IT MUST BE
 DOWNSTREAM PER THE 2017 FBC SECTION R 3108.1 HORIZONTAL
 WET VENT PERMITTED.
  
 2. PLEASE SHOW THAT SHOWER PAN IS RECESSED IN PS1.0, IF
 THE SHOWER PAN IS NOT RECEDED IT WILL REQUIRE LINING
 PER 2017 FBC SECTION R 2709.2.
  
 NOTE: SHOWER PAN MUST HAVE A SLOPED MORTAR BED THAT IS
 PRE-PITCHED BENEATH PRIOR TO LINER INSTALLATION OF 1/4"
 IN PER FOOT TOWARD THE DRAIN, MUST HAVE DAM CORNER,
 BACKING AROUND THE PERIMETER AND BEFORE FINAL MORTAR
 APPLICATION PLACE SOME PEA GRAVEL OVER WEEP HOLES SO
 THE MORTAR DOES NOT COVER THEM PER MANUFACTURES
 SPECIFICATIONS. (PLEASE PLACE THIS NOTE IF NOT RECESSED
 AND OR SHOW A DETAIL, IF RECESSED PLEASE INCLUDE SEAT
 IN THE RECESS TOTAL DIMENSION AS SEAT WILL PECULATE
 INTO RECESS OF PAN).
  
 3. THERE ARE 2 E1.0 PAGES PLEASE LABEL TO DISTINGUISH
 IE, EP1.1 PER THE WPB AMENDMENTS TO THE FBC SEC.107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 4. A SUB PLUMBING PERMIT IS REQUIRED BY A LICENSED
 CONTRACTOR FOR THE SCOPE OF WORK PER THE WPB AMENDMENTS
 TO THE FBC SEC. 105.1.
  
 5. HOW IS CABANA GOING TO HAVE HOT WATER, IF FROM MAIN
 HOUSE AND LINES ARE BEING RAN UNDERGROUND, THE HOT ONLY
 MUST BE INSULATED WITH A MINIMUM R- 3 INSULATION PER
 THE 2017 FBC RE SECTION 403.5.3.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION, MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  