| 2020-03-23 18:57:04 | 03/23/2020 PLUMBING 1ST REVIEW **DENIED** WITH COMMENTS |
| | |
| | NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS |
| | TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE |
| | GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS. |
| | |
| | 1. ON ISOMETRIC (E1.0) DRAWING KITCHEN SINK CANNOT |
| | DISCHARGE INTO WET VET OF A BATHROOM GROUP IT MUST BE |
| | DOWNSTREAM PER THE 2017 FBC SECTION R 3108.1 HORIZONTAL |
| | WET VENT PERMITTED. |
| | |
| | 2. PLEASE SHOW THAT SHOWER PAN IS RECESSED IN PS1.0, IF |
| | THE SHOWER PAN IS NOT RECEDED IT WILL REQUIRE LINING |
| | PER 2017 FBC SECTION R 2709.2. |
| | |
| | NOTE: SHOWER PAN MUST HAVE A SLOPED MORTAR BED THAT IS |
| | PRE-PITCHED BENEATH PRIOR TO LINER INSTALLATION OF 1/4" |
| | IN PER FOOT TOWARD THE DRAIN, MUST HAVE DAM CORNER, |
| | BACKING AROUND THE PERIMETER AND BEFORE FINAL MORTAR |
| | APPLICATION PLACE SOME PEA GRAVEL OVER WEEP HOLES SO |
| | THE MORTAR DOES NOT COVER THEM PER MANUFACTURES |
| | SPECIFICATIONS. (PLEASE PLACE THIS NOTE IF NOT RECESSED |
| | AND OR SHOW A DETAIL, IF RECESSED PLEASE INCLUDE SEAT |
| | IN THE RECESS TOTAL DIMENSION AS SEAT WILL PECULATE |
| | INTO RECESS OF PAN). |
| | |
| | 3. THERE ARE 2 E1.0 PAGES PLEASE LABEL TO DISTINGUISH |
| | IE, EP1.1 PER THE WPB AMENDMENTS TO THE FBC SEC.107.2.1 |
| | INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | |
| | 4. A SUB PLUMBING PERMIT IS REQUIRED BY A LICENSED |
| | CONTRACTOR FOR THE SCOPE OF WORK PER THE WPB AMENDMENTS |
| | TO THE FBC SEC. 105.1. |
| | |
| | 5. HOW IS CABANA GOING TO HAVE HOT WATER, IF FROM MAIN |
| | HOUSE AND LINES ARE BEING RAN UNDERGROUND, THE HOT ONLY |
| | MUST BE INSULATED WITH A MINIMUM R- 3 INSULATION PER |
| | THE 2017 FBC RE SECTION 403.5.3. |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & |
| | REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION, MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |