Plan Review Notes
Plan Review Notes For Permit 20020928
Permit Number 20020928
Review Stop G
Sequence Number 1
Notes
Date Text
2020-02-28 07:16:3002/27/2020 1ST GAS REVIEW **DENIED** WITH COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 1. GAS RISER DIAGRAM REQUIRED WPB AMENDMENTS TO THE
 FBC SEC. 107.3.5.3 (12) RESIDENTIAL GAS.
  
 2. ON THE GAS ISOMETRIC DRAWING CLEARLY SHOWS THE
 LENGTH OF ALL CUT SECTIONS OF PIPE PER 2017 FBC RES.
 SECS. G2413.4.1, G2413.4.2.
  
 3. ON ISOMETRIC LIST THE BTU LOAD OF EACH APPLIANCE AND
 THE TOTAL BTU LOAD ON THE SYSTEM. REFER TO THE 2017 FBC
 RES. SEC. G2413.
  
 4. ON ISOMETRIC PLEASE SHOW ALL DRIP LEGS, SHUTOFF
 VALVE AND UNIONS IN FRONT OF REGULATOR 1' OF EITHER
 SIDE PER THE 2017 FBC FG SEC 410.2.
  
  
 5. SUBMIT COMBUSTION AIR CALCULATIONS FOR THE GAS
 APPLIANCES (RANGE). WHERE IS COMBUSTION AIR PROVIDED BY
 THE BUILDING'S MECHANICAL VENTILATION SYSTEM, THE
 SYSTEM SHALL PROVIDE THE SPECIFIED COMBUSTION AIR RATE
 IN ADDITION TO THE REQUIRED VENTILATION AIR PER THE
 2017 FBC RES. SEC. G2407.9.3. COMBINED COMBUSTION AIR
 AND VENTILATION AIR SYSTEM.
  
 6. SUBMIT MANUFACTURER'S SPECIFICATION
 SHEETS/INSTALLATION MANUAL FOR ALL GAS EQUIPMENT
 (GENERATOR, RANGE AND BBQ) TO VERIFY COMPLIANCE WITH
 2017 FBC RES. SEC. G2408.1.
  
 7. GAS APPLIANCES SHALL BE LISTED AND LABELED. THE
 INSTALLATION MANUALS FOR ALL GAS APPLIANCES/EQUIPMENT
 SHALL BE ONSITE AT THE TIME OF INSPECTION PER THE 2017
 FBC RES. SEC. G2413.2 AND G2404.3.
  
 8. CLEARLY SHOW THE DISTANCE OF THE TANK FROM THE
 EXTERIOR ADJACENT PROPERTY LINES AND DRIVEWAY, THE
 DISTANCE OF THE TANK FROM ALL SOURCES OF IGNITION,
 OTHER CONTAINERS, BUILDINGS, AND THE LOCATION OF ANY
 BUILDING OPENINGS BELOW THE RELIEF VALVE OF THE TANK
 PER NFPA 58, TABLE 3-2.2.2.
  
 9. CLEARLY INDICATE ON THE TIE-DOWN SHEET IF THE LP
 TANK TIE-DOWN METHOD AND IF YOU ARE USING STRAPS OR
 CABLE, (THE ONE PROVIDED IN FOR ABOVE) IF CABLE HOW IS
 IT PROTECTED FOR THE LP TANK AND APPURTENANCES PER NFPA
 58. WPB AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION
 ON CONSTRUCTION DOCUMENTS.
  
 10. PROVIDE THE SIZE OF THE HOLD-DOWN CABLES/STRAPS FOR
 THE TANK AND THE TYPE AND LENGTH OF GROUND ANCHORS TO
 BE INSTALLED TO PREVENT FLOTATION. NFPA 58 SEC.
 6.6.1.6.
  
 11. SHOW THE DEPTH OF THE CONTAINER BELOW GRADE. COMPLY
 WITH NFPA 58 SEC. 6.6.6.1.
  
 12. SUBMIT TWO COPIES OF A HOUSE PLAN SHOWING THE
 LOCATION OF THE GENERATOR AND THE LOCATION AND DISTANCE
 OF ANY OPERABLE DOORS, SOFFIT VENT, LOT LINE OR WINDOWS
 IN RELATION TO THE GENERATOR. THE LOCATION OF THE
 GENERATOR SHALL COMPLY WITH THE MANUFACTURER'S
 INSTALLATION INSTRUCTIONS. THE HOUSE PLAN CAN BE
 HAND-DRAWN PER THE WPB AMENDMENTS TO THE FBC SEC.
 107.2.1. INFORMATION ON CONSTRUCTION DOCUMENTS.
  
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION, MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  