| 2020-02-28 07:16:30 | 02/27/2020 1ST GAS REVIEW **DENIED** WITH COMMENTS |
| | |
| | NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS |
| | TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE |
| | GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS. |
| | |
| | 1. GAS RISER DIAGRAM REQUIRED WPB AMENDMENTS TO THE |
| | FBC SEC. 107.3.5.3 (12) RESIDENTIAL GAS. |
| | |
| | 2. ON THE GAS ISOMETRIC DRAWING CLEARLY SHOWS THE |
| | LENGTH OF ALL CUT SECTIONS OF PIPE PER 2017 FBC RES. |
| | SECS. G2413.4.1, G2413.4.2. |
| | |
| | 3. ON ISOMETRIC LIST THE BTU LOAD OF EACH APPLIANCE AND |
| | THE TOTAL BTU LOAD ON THE SYSTEM. REFER TO THE 2017 FBC |
| | RES. SEC. G2413. |
| | |
| | 4. ON ISOMETRIC PLEASE SHOW ALL DRIP LEGS, SHUTOFF |
| | VALVE AND UNIONS IN FRONT OF REGULATOR 1' OF EITHER |
| | SIDE PER THE 2017 FBC FG SEC 410.2. |
| | |
| | |
| | 5. SUBMIT COMBUSTION AIR CALCULATIONS FOR THE GAS |
| | APPLIANCES (RANGE). WHERE IS COMBUSTION AIR PROVIDED BY |
| | THE BUILDING'S MECHANICAL VENTILATION SYSTEM, THE |
| | SYSTEM SHALL PROVIDE THE SPECIFIED COMBUSTION AIR RATE |
| | IN ADDITION TO THE REQUIRED VENTILATION AIR PER THE |
| | 2017 FBC RES. SEC. G2407.9.3. COMBINED COMBUSTION AIR |
| | AND VENTILATION AIR SYSTEM. |
| | |
| | 6. SUBMIT MANUFACTURER'S SPECIFICATION |
| | SHEETS/INSTALLATION MANUAL FOR ALL GAS EQUIPMENT |
| | (GENERATOR, RANGE AND BBQ) TO VERIFY COMPLIANCE WITH |
| | 2017 FBC RES. SEC. G2408.1. |
| | |
| | 7. GAS APPLIANCES SHALL BE LISTED AND LABELED. THE |
| | INSTALLATION MANUALS FOR ALL GAS APPLIANCES/EQUIPMENT |
| | SHALL BE ONSITE AT THE TIME OF INSPECTION PER THE 2017 |
| | FBC RES. SEC. G2413.2 AND G2404.3. |
| | |
| | 8. CLEARLY SHOW THE DISTANCE OF THE TANK FROM THE |
| | EXTERIOR ADJACENT PROPERTY LINES AND DRIVEWAY, THE |
| | DISTANCE OF THE TANK FROM ALL SOURCES OF IGNITION, |
| | OTHER CONTAINERS, BUILDINGS, AND THE LOCATION OF ANY |
| | BUILDING OPENINGS BELOW THE RELIEF VALVE OF THE TANK |
| | PER NFPA 58, TABLE 3-2.2.2. |
| | |
| | 9. CLEARLY INDICATE ON THE TIE-DOWN SHEET IF THE LP |
| | TANK TIE-DOWN METHOD AND IF YOU ARE USING STRAPS OR |
| | CABLE, (THE ONE PROVIDED IN FOR ABOVE) IF CABLE HOW IS |
| | IT PROTECTED FOR THE LP TANK AND APPURTENANCES PER NFPA |
| | 58. WPB AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION |
| | ON CONSTRUCTION DOCUMENTS. |
| | |
| | 10. PROVIDE THE SIZE OF THE HOLD-DOWN CABLES/STRAPS FOR |
| | THE TANK AND THE TYPE AND LENGTH OF GROUND ANCHORS TO |
| | BE INSTALLED TO PREVENT FLOTATION. NFPA 58 SEC. |
| | 6.6.1.6. |
| | |
| | 11. SHOW THE DEPTH OF THE CONTAINER BELOW GRADE. COMPLY |
| | WITH NFPA 58 SEC. 6.6.6.1. |
| | |
| | 12. SUBMIT TWO COPIES OF A HOUSE PLAN SHOWING THE |
| | LOCATION OF THE GENERATOR AND THE LOCATION AND DISTANCE |
| | OF ANY OPERABLE DOORS, SOFFIT VENT, LOT LINE OR WINDOWS |
| | IN RELATION TO THE GENERATOR. THE LOCATION OF THE |
| | GENERATOR SHALL COMPLY WITH THE MANUFACTURER'S |
| | INSTALLATION INSTRUCTIONS. THE HOUSE PLAN CAN BE |
| | HAND-DRAWN PER THE WPB AMENDMENTS TO THE FBC SEC. |
| | 107.2.1. INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & |
| | REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION, MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |