| Plan Review Notes For Permit 20020926 |
| Permit Number |
20020926 |
|
| Review Stop |
B |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2020-03-19 16:34:34 | GENERATOR | | | REVIEWED BY ROGER MCPHERSON | | | 561-805-6716 | | | [email protected] | | | | | | CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107.2.1 | | | 1) PLEASE PROVIDE SIGNED AND SEALED SITE SPECIFIC WIND | | | DESIGN PRESSURE FROM AN ARCHITECT OR ENGINEER PER NOTE | | | NUMBER 2 ON THE SLAB ENGINEERING DRAWING. | | | 2) PLEASE SHOW GENERATOR EXHAUST AT 10 FEET AWAY FROM | | | AN OPENING INTO THE HOUSE PER FBC R303.5.1 |
|