Plan Review Notes
Plan Review Notes For Permit 20020920
Permit Number 20020920
Review Stop E
Sequence Number 2
Notes
Date Text
2020-07-10 09:17:53ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 FLORIDA BUILDING CODE 2017 6TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED
 NFPA 70 2014 EDITION
  
 JAKE LEAHY BN, BU, PX
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 ES LICENSE FOR "LIMITED ENERGY SYSTEM SPECIALTY" IS NOT
 ALLOWED TO WIRE SYSTEMS THAT CONNECT TO THE FIRE ALARM
 SYSTEM. SEE SCOPE BELOW
  
  
 (4) LIMITED ENERGY SYSTEMS SPECIALTY. THE SCOPE OF
 CERTIFICATION OF A LIMITED ENERGY SYSTEMS SPECIALTY
 CONTRACTOR INCLUDES THE INSTALLATION, REPAIR,
 FABRICATION, ERECTION, ALTERATION, ADDITION TO, OR
 DESIGN OF ELECTRICAL WIRING, FIXTURES, APPLIANCES,
 THERMOSTATS, APPARATUS, RACEWAYS, CONDUIT, AND FIBER
 OPTICS (TRANSMISSION OF LIGHT OVER STRANDED GLASS) OR
 ANY PART THEREOF NOT TO EXCEED 98 VOLTS, (RMS). THE
 SCOPE OF WORK OF THIS LICENSE DOES NOT INCLUDE
 INSTALLATION, REPAIR, FABRICATION, ERECTION,
 ALTERATION, ADDITION TO, OR DESIGN OF ELECTRICAL
 WIRING, FIXTURES, APPLIANCES, THERMOSTATS, APPARATUS,
 RACEWAYS, CONDUIT, THAT ARE PART OF AN ALARM SYSTEM.
 (A) THE SCOPE OF CERTIFICATION IS LIMITED TO ELECTRICAL
 CIRCUITS AND EQUIPMENT AS SET FORTH IN SECTION
 489.505(7), F.S.
 (B) THE SCOPE OF CERTIFICATION SHALL NOT INCLUDE WORK
 PERFORMED BY PUBLIC UTILITIES EXEMPT UNDER THE TERMS OF
 SECTION 489.503(4), F.S., OR EXEMPT DUE TO THE
 REGULATORY JURISDICTION OF THE FLORIDA PUBLIC SERVICE
 COMMISSION.
 (C) THE SCOPE OF WORK OF THIS LICENSE MAY ALSO BE
 PERFORMED BY THE FOLLOWING CERTIFIED AND REGISTERED
 LICENSE CATEGORIES: UNLIMITED ELECTRICAL CONTRACTOR,
 ALARM SYSTEM CONTRACTOR I, ALARM SYSTEM CONTRACTOR II,
 AND RESIDENTIAL ELECTRICAL CONTRACTOR.
  