Plan Review Notes
Plan Review Notes For Permit 20020920
Permit Number 20020920
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2020-03-11 11:08:05THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1A) DOES THE SUBMITTING AND INSTALLING CONTRACTOR HAVE
 A FCC LICENSE?
  
 PLEASE PROVIDE.
  
  
  
 1B) THERE IS NO HEAT MAP / COLOR SPECTRUM REPORT OF
 EACH FLOOR PLAN SHOWING THE AREAS THAT WOULD REQUIRE
 ENHANCEMENT.
  
 24.5.2.2 RADIO COVERAGE. RADIO COVERAGE SHALL BE
 PROVIDED
 THROUGHOUT THE BUILDING AS A PERCENTAGE OF FLOOR AREA
 AS SPECIFIED
 IN 24.5.2.2.1 THROUGH 24.5.2.2.3.
 24.5.2.2.1 CRITICAL AREAS. CRITICAL AREAS, SUCH AS THE
 FIRE COMMAND
 CENTER(S), THE FIRE PUMP ROOM(S), EXIT STAIRS, EXIT
 PASSAGEWAYS,
 ELEVATOR LOBBIES, STANDPIPE CABINETS, SPRINKLER
 SECTIONAL
 VALVE LOCATIONS, AND OTHER AREAS DEEMED CRITICAL BY THE
 AUTHORITY HAVING JURISDICTION, SHALL BE PROVIDED WITH
 99 PERCENT
 FLOOR AREA RADIO COVERAGE.
 24.5.2.2.2 GENERAL BUILDING AREAS. GENERAL BUILDING
 AREAS
 SHALL BE PROVIDED WITH 90 PERCENT FLOOR AREA RADIO
 COVERAGE.
  
 PLEASE PROVIDE A REPORT SHOWING ALL AREAS, THUS
 DEFENDING THE POSITION OF THE EQUIPMENT
  
  
 2) THERE IS AN INDICATION OF RUNNING CABLE UP THROUGH
 EXISTING PENETRATIONS.
  
 PLEASE BE SPECIFIC AND IDENTIFY THOSE PENETRATIONS.
  
  
 3) THERE ARE NO PRODUCT SHEETS INDUCING LISTINGS AND
 COMBATABILITY.
  
 24.5.2.5.2 COMPONENT ENCLOSURES. ALL REPEATER,
 TRANSMITTER, RECEIVER,
 SIGNAL BOOSTER COMPONENTS, AND BATTERY SYSTEM
 COMPONENTS
 SHALL BE CONTAINED IN A NEMA4- OR 4X-TYPE ENCLOSURE(S).
  
 PLEASE PROVIDE.
  
  
 4) THERE ARE INDICATIONS OF SPLITTERS AND COAX CABLE AS
 PLENUM RATED, BUT ARE THEY FIRE RATED?
  
 27.7.1.6 WIRING INSIDE BUILDINGS.
 27.7.1.6.1 AT THE COMMUNICATIONS CENTER, ALL
 CONDUCTORS,
 CABLES, AND FIBER-OPTIC CABLES SHALL EXTEND AS DIRECTLY
 AS POSSIBLE
 TO THE OPERATIONS CENTER IN CONDUITS, DUCTS, SHAFTS,
 RACEWAYS,
 OR OVERHEAD RACKS AND TROUGHS LISTED OR IDENTIFIED AS
 SUITABLE
 TO PROVIDE PROTECTION AGAINST PHYSICAL DAMAGE.
 27.7.1.6.2* WHERE INSTALLED IN BUILDINGS, CONDUCTORS
 AND
 FIBER-OPTIC CABLES SHALL BE INSTALLED IN ANY OF THE
 FOLLOWING WIRING
 METHODS:
 (1) ELECTRICAL METALLIC TUBING
 (2) INTERMEDIATE METAL CONDUIT
 (3) RIGID METAL CONDUIT
 EXCEPTION: RIGID NONMETALLIC CONDUIT SHALL BE PERMITTED
 WHERE APPROVED
 BY THE AUTHORITY HAVING JURISDICTION.
  
 HOW WILL SPLITTERS BE PROTECTED?
  
  
 5) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
  
 6) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  