Plan Review Notes
Plan Review Notes For Permit 20020878
Permit Number 20020878
Review Stop E
Sequence Number 2
Notes
Date Text
2020-07-08 08:57:54CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2014 5TH EDITION
 FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2014
 5TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2014 5TH EDITION,
 PART VIII ELECTRICAL
 NEC = NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 FLORIDA BUILDING CODE 2017 6TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED
 NFPA 70 2014 EDITION
  
 JAKE LEAHY BN, BU, PX
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 1) COMMENT FROM LAST REVIEW NOT COMPLIED.
  
 2) AVAILABLE FAULT CURRENT RATING FOR THE SERVICE
 EQUIPMENT IS REQUIRED. 110.9, 110.10, 100.24 FOR LABEL
  
 PROVIDE AVAILABLE SHORT CIRCUIT CALCULATION FOR EACH
 PANEL INCLUDING INFORMATION FROM THE POWER COMPANY
 STATING WHAT THE AVAILABLE SHORT CIRCUIT CURRENT IS FOR
 THE SERVICE TO CONFIRM THE STATED AIC RATING OF THE
 SERVICE EQUIPMENT AND DOWNSTREAM PANELS IS ADEQUATE.
 NEC 110.9, 110.10
  
 PROVIDE LABEL(S) FOR SERVICE EQUIPMENT AS REQUIRED BY
 110.24
  
 3) PANEL BOARD NEEDS TO BE LISTED NEEDS110.3, 230.66
 MARKING SERVICE EQUIPMENT RATED AT 1000 VOLTS OR LESS
 SHALL BE MARKED TO IDENTIFY IT AS BEING SUITABLE FOR
 USE AS SERVICE EQUIPMENT. ALL SERVICE EQUIPMENT SHALL
 BE LISTED. INDIVIDUAL METER SOCKET ENCLOSURES SHALL NOT
 BE CONSIDERED SERVICE EQUIPMENT.