| Plan Review Notes For Permit 20020877 |
| Permit Number |
20020877 |
|
| Review Stop |
E |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2020-07-08 08:33:31 | CODES IN EFFECT: | | | FBC = FLORIDA BUILDING CODE 2014 5TH EDITION | | | FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 | | | 5TH EDITION | | | FBC RE = FLORIDA RESIDENTIAL CODE 2014 5TH EDITION, | | | PART VIII ELECTRICAL | | | NEC = NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE | | | FS = FLORIDA STATUTES | | | | | | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | | | FLORIDA BUILDING CODE 2017 6TH EDITION | | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED | | | NFPA 70 2014 EDITION | | | | | | JAKE LEAHY BN, BU, PX | | | ELECTRICAL PLANS EXAMINER II | | | 561-805-6713 | | | [email protected] | | | | | | 1) COMMENT FROM LAST REVIEW NOT COMPLIED. | | | | | | 2) AVAILABLE FAULT CURRENT RATING FOR THE SERVICE | | | EQUIPMENT IS REQUIRED. 110.9, 110.10, 100.24 FOR LABEL | | | | | | PROVIDE AVAILABLE SHORT CIRCUIT CALCULATION FOR EACH | | | PANEL INCLUDING INFORMATION FROM THE POWER COMPANY | | | STATING WHAT THE AVAILABLE SHORT CIRCUIT CURRENT IS FOR | | | THE SERVICE TO CONFIRM THE STATED AIC RATING OF THE | | | SERVICE EQUIPMENT AND DOWNSTREAM PANELS IS ADEQUATE. | | | NEC 110.9, 110.10 | | | | | | PROVIDE LABEL(S) FOR SERVICE EQUIPMENT AS REQUIRED BY | | | 110.24 | | | | | | 3) PANEL BOARD NEEDS TO BE LISTED NEEDS110.3, 230.66 | | | MARKING SERVICE EQUIPMENT RATED AT 1000 VOLTS OR LESS | | | SHALL BE MARKED TO IDENTIFY IT AS BEING SUITABLE FOR | | | USE AS SERVICE EQUIPMENT. ALL SERVICE EQUIPMENT SHALL | | | BE LISTED. INDIVIDUAL METER SOCKET ENCLOSURES SHALL NOT | | | BE CONSIDERED SERVICE EQUIPMENT. |
|