| Plan Review Notes For Permit 20020861 |
| Permit Number |
20020861 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2020-02-22 14:30:23 | ***CORRECTIONS*** | | | PETER E VALENTI | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6673 | | | | | | FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) | | | FBC B = FBC BUILDING | | | FBC EB = FBC EXISTING BUILDING | | | FBC A = FBC ACCESSIBILITY | | | FBC EC = FBC ENERGY CONSERVATION | | | FBC R = FBC RESIDENTIAL | | | FBC M = FBC MECHANICAL | | | | | | BUILDING REVIEW DENIED: | | | | | | FBC B 3103.1.1, TEMPORARY STRUCTURES AND USES SHALL | | | CONFORM TO THE STRUCTURAL STRENGTH, FIRE SAFETY, MEANS | | | OF EGRESS, ACCESSIBILITY, LIGHT, VENTILATION AND | | | SANITARY REQUIREMENTS OF THIS CODE AS NECESSARY TO | | | ENSURE PUBLIC HEALTH, SAFETY AND GENERAL WELFARE. | | | | | | PLEASE PROVIDE THE FOLLOWING: | | | | | | 1) FBC CHAPTER 16, PROVIDE STRUCTURAL EVALUATION OF | | | STRUCTURE SIGNED AND SEALED BY A DESIGN PROFESSIONAL. | | | | | | 2) FBC CHAPTER 10, PROVIDE A LIFE SAFETY PLAN | | | A) STATE THE OCCUPANT LOAD | | | B) IDENTIFY THE MEANS OF EGRESS | | | C) IDENTIFY THE PATH OF TRAVEL | | | | | | 3) FBC A 201.3 IDENTIFY THE ACCESSIBLE ROUTE ON SITE | | | PLAN | | | 4) FBC B 1008.2.1 LIGHTING IS REQUIRED GREATER THAN 1 | | | FOOT CANDLE | | | 5) FBC B 1203 VENTILLATION IS REQUIRED | | | 6) FBC B TABLE 2902.1, PROVIDE ACCESSIBLE PORTABLE | | | RESTROOMS/SANITARY FACILITIES PER FBC TABLE 2902.1 IF | | | PERMANENT ACCESSIBLE FACILITIES ARE NOT LOCATED WITHIN | | | 500' OF TENT. | | | | | | |
|