2020-03-06 06:51:34ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. NO VALUE OR SQUARE FOOTAGE LISTED ON PERMIT
 APPLICATION. FBC 107.2.1
  
 2. NO 120V DISCONNECT WITHIN SIGHT OF SIGN. PROVIDE
 CORRECTION. NEC 600.6A1
  
 3. ASTRONOMICAL TIMECLOCK REQUIRED PER FBC CE 405.2.5
  
 ALL EXTERIOR LIGHTING NOT EXEMPTED BY FBC 405.1 SHALL
 HAVE AUTOMATIC CONTROLS TO TURN OFF AT DAYLIGHT OR WHEN
 NOT REQUIRED. CONTROLS SHALL BE PHOTOSENSOR & TIME
 CLOCK OR ASTRONOMICAL TIME SWITCH. ALL TIME SWITCHES
 SHALL BE CAPABLE OF RETAINING PROGRAMING DURING A LOSS
 OF POWER FOR A MINIMUM OF 10 HOURS. FBC-EC 405.2.5
  
 4. PLANS HAS REFERENCED INCORRECT NEC AND FBC EDITIONS.
 THE CURRENT ADOPTED EDITION OF THE NEC IS 2014, THE
 PLAN HAS 2011 ON IT AND THE CURRENT ADOPTED EDITION OF
 THE FBC IS 2017 AND 2014 IS REFERENCED.
  
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
 CODES IN EFFECT:
  
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2017 6TH ED.
 FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 V/R,
  
 FRANK GIAQUINTO III
 ELECTRICAL INSPECTOR
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH