| 2020-03-06 06:51:34 | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| | |
| | 1. NO VALUE OR SQUARE FOOTAGE LISTED ON PERMIT |
| | APPLICATION. FBC 107.2.1 |
| | |
| | 2. NO 120V DISCONNECT WITHIN SIGHT OF SIGN. PROVIDE |
| | CORRECTION. NEC 600.6A1 |
| | |
| | 3. ASTRONOMICAL TIMECLOCK REQUIRED PER FBC CE 405.2.5 |
| | |
| | ALL EXTERIOR LIGHTING NOT EXEMPTED BY FBC 405.1 SHALL |
| | HAVE AUTOMATIC CONTROLS TO TURN OFF AT DAYLIGHT OR WHEN |
| | NOT REQUIRED. CONTROLS SHALL BE PHOTOSENSOR & TIME |
| | CLOCK OR ASTRONOMICAL TIME SWITCH. ALL TIME SWITCHES |
| | SHALL BE CAPABLE OF RETAINING PROGRAMING DURING A LOSS |
| | OF POWER FOR A MINIMUM OF 10 HOURS. FBC-EC 405.2.5 |
| | |
| | 4. PLANS HAS REFERENCED INCORRECT NEC AND FBC EDITIONS. |
| | THE CURRENT ADOPTED EDITION OF THE NEC IS 2014, THE |
| | PLAN HAS 2011 ON IT AND THE CURRENT ADOPTED EDITION OF |
| | THE FBC IS 2017 AND 2014 IS REFERENCED. |
| | |
| | |
| | END OF COMMENTS. |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| | PREVIOUSLY REVIEWED SHEETS. |
| | CODES IN EFFECT: |
| | |
| | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE 2017 6TH ED. |
| | FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2017 |
| | 6TH EDITION |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| | 6TH EDITION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE |
| | FS = FLORIDA STATUTES |
| | |