| Plan Review Notes For Permit 20020852 |
| Permit Number |
20020852 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2020-03-04 11:45:05 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE | | | MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | | | | 1) THE SUBMITTED PLANS INDICATED A LIMITED FIRE ALARM | | | SYSTEM. | | | | | | PLEASE PROVIDE THE OCCUPANCY CLASSIFICATION PER THE | | | FLORIDA FIRE PREVENTION CODE. | | | | | | | | | | | | 2) THE DOES NOT APPEAR TO BE SUFFICINET OCCUPANT | | | NOTIFICATION IN ALL THE ROOMS. | | | | | | PER # 1 ABOVE , PLEASE REVIEW CODE COMPLIANT | | | NOTIFICATION IN ALL APPLICABLE AREAS OR JUSTIFY WITH A | | | SPECIFIC DETAILS IN A WRITTEN NARRATIVE. | | | | | | | | | | | | 3) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET | | | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE | | | ABOVE. | | | | | | | | | | | | 4) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE | | | RE-SUBMITTAL OF THE ABOVE. | | | | | | | | | | | | | | | | | | | | | PETER LEDUC | | | FIRE MARSHAL | | | 561-804-4709 | | | [email protected] | | | |
|