| Plan Review Notes For Permit 20020841 |
| Permit Number |
20020841 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2020-03-23 10:46:09 | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | | | JAKE LEAHY | | | ELECTRICAL PLANS EXAMINER II | | | 561-805-6713 | | | [email protected] | | | | | | 1) LIGHTS ON COLUMNS NEXT TO THE POOL PLEASE SHOW THE | | | DIMENSION OF LIGHTS FROM POOL. | | | | | | FBC RESIDENTIAL CODE E4203.4 LIGHTS TO BE AT LEAST 5' | | | FROM THE INSIDE WALL OF THE POOL AND 12' UP OF GRADE. | | | | | | 2) ALL 15 AND 20 AMPERE RECEPTACLE OUTLETS INSTALLED | | | OUTSIDE SHALL HAVE GFCI PROTECTION. | | | | | | FBC RESIDENTIAL CODE E3902.3 | | | | | | 3) NEED TO SUBMIT A PANEL SCHEDULE | | | | | | FBC RESIDENTIAL CODE E3706.2 | | | | | | 4) LOAD CALCULATION REQUIRED FOR ADDITIONAL LOADS. | | | | | | 220.16(A)(1) 2014 NEC | | 2020-03-22 09:20:34 | JL |
|