| 2020-05-28 14:46:15 | 3RD REVIEW FBC-2017 PLUMBING |
| | PERMIT #20020833 |
| | 5/282020 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017 |
| | FBC ACC- FLORIDA ACCESSIBILITY CODE SIXTH ADDITION 2017 |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| | 2017 |
| | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH |
| | EDITION 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | THE REVISED PLANS ARE COMPLIANT FOR THE NEW TENANT |
| | OCCUPANCY ONLY. PLEASE REVIEW COMMENT #1 BELOW |
| | CONCERNING THE MAIN OCCUPANCY. |
| | |
| | 1) SHEET A0.0: THE OCCUPANT LOAD CALCULATIONS INDICATE |
| | A SHORTAGE OF ONE MALE AND ONE FEMALE WATER CLOSET FOR |
| | THE MAIN OCCUPANCY THE REVISED OCCUPANT LOAD FOR THE |
| | MAIN OCCUPANCY WITH THE REDUCTION OF 21 PERSONS IN THE |
| | NEW TENANT SPACE IS 157 PERSONS. (178 PERSONS 21 |
| | PERSONS = 157), (157/2 = 79 MALE AND 79 FEMALE). BASED |
| | ON TABLE 403.3 WATER CLOSETS ARE REQUIRED FOR EACH SEX, |
| | HOWEVER THE EXISTING COMMUNAL BATHROOMS SHOWN IN THE |
| | KEY PLAN INDICATE 1 WATER CLOSET AND 1 URINAL FOR THE |
| | MEN'S ROOM, AND 2 WATER CLOSETS FOR THE WOMEN'S ROOM. |
| | REFER TO SHEET A1.0: PRIOR TO SEPARATING THE NEW TENANT |
| | SPACE FROM THE MAIN, ACCESS WAS BEING PROVIDED FROM THE |
| | COMMON CORRIDOR TO THE TWO TOILET ROOMS THAT ARE NOW TO |
| | BE DEMOLISHED. IT APPEARS THAT THE RESULT OF THE |
| | PROPOSED DEMOLITION WILL CAUSE THE SHORTAGE FOR THE |
| | ENTIRE FLOOR, NEW TENANT SPACE INCLUDED. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |