| 2020-03-02 14:00:17 | 2017 FBC- BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 20020833 |
| | ADD: 1411 N FLAGLER DR. SUITE: 3000 |
| | CONT: RITEWAY CONTRACTING & PAINTING |
| | TEL: 561-740-7999 |
| | E-MAIL: [email protected] |
| | |
| | 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION. |
| | |
| | 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW |
| | CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES |
| | SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA |
| | BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: MONDAY, MARCH 02/2020 |
| | ACTION: DENIED |
| | |
| | 1) THE COVERSHEET A-0.0 THE KEY PLAN INDICATES THE |
| | CONSTRUCTION TYPE AS III-B / FULLY SPRINKLERED. PLEASE |
| | NOTE THIS IS A 9 STORY BUILDING WITH BUSINESS |
| | OCCUPANCIES. PLEASE REVIEW THE 2017 FBC-B TABLE 504.4 |
| | FOR A BUSINESS OCCUPANCY TABLE 504.4 INDICATES THE |
| | MINIMUM BUILDING TYPE WOULD BE I-B CONSTRUCTION. PLEASE |
| | CORRECT THE PLANS. THANK YOU. |
| | |
| | 2) THE PERMIT APPLICATION INDICATES THE CONTRACT VALUE |
| | IS $70,000.00 DOLLARS IN VALUE. DISPROPORTIONATE COST. |
| | 2017 FBC-ACCESSIBILITY CODE SECTION 202.4.1. PLEASE |
| | PROVIDE A LETTER EITHER FROM THE CONTRACTOR OR DESIGNER |
| | OF RECORD ON THEIR LETTERHEAD WHERE UP TO 20 % OF THE |
| | CONTRACT VALUE ($14,000.00) IS GOING TO BE SPENT IN |
| | ACCESSIBLE UPGRADES TO THE PROJECT. IF ALL EXISTING |
| | CONDITIONS ARE COMPLETED (COMPLIED) BEFORE |
| | DISPROPORTIONATION COST IS MET A LETTER IS NOT |
| | REQUIRED. SHOW COMPLIANCE WITH THE: |
| | 2017 FBC-ACCESSIBILITY CODE SECTION 202.4.1 |
| | DISPROPORTIONATE COST. ALTERATIONS MADE TO PROVIDE AN |
| | ACCESSIBLE PATH OF TRAVEL TO THE ALTERED AREA WILL BE |
| | DEEMED DISPROPORTIONATE TO THE OVERALL ALTERATION WHEN |
| | THE COST EXCEEDS 20% OF THE COST OF THE ALTERATION TO |
| | THE PRIMARY FUNCTION AREA. COSTS THAT MAY BE COUNTED AS |
| | EXPENDITURES REQUIRED TO PROVIDE AN ACCESSIBLE PATH OF |
| | TRAVEL MAY INCLUDE: (I) COSTS ASSOCIATED WITH PROVIDING |
| | AN ACCESSIBLE ENTRANCE AND AN ACCESSIBLE ROUTE TO THE |
| | ALTERED AREA; (II) COSTS ASSOCIATED WITH MAKING |
| | RESTROOMS ACCESSIBLE, SUCH AS INSTALLING GRAB BARS, |
| | ENLARGING TOILET STALLS, INSULATING PIPES, OR |
| | INSTALLING ACCESSIBLE FAUCET CONTROLS; (III) COSTS |
| | ASSOCIATED WITH PROVIDING ACCESSIBLE TELEPHONES, SUCH |
| | AS RELOCATING THE TELEPHONE TO AN ACCESSIBLE HEIGHT, |
| | INSTALLING AMPLIFICATION DEVICES, OR INSTALLING A TEXT |
| | TELEPHONE (TTY); (IV) COSTS ASSOCIATED WITH RELOCATING |
| | AN INACCESSIBLE DRINKING FOUNTAIN. |
| | |
| | 2A) SHEET A-1.0. IT WOULD APPEAR THAT 2 OF THE EXISTING |
| | DOORWAYS (DOORS 303 & 306) WILL NOT COMPLY WITH THE |
| | ACCESSIBILITY CODE SECTION CODE 404.2.4 MANEUVERING |
| | CLEARANCES. DOORS. MINIMUM MANEUVERING CLEARANCES AT |
| | DOORS AND GATES SHALL COMPLY WITH 404.2.4. MANEUVERING |
| | CLEARANCES SHALL EXTEND THE FULL WIDTH OF THE DOORWAY |
| | AND THE REQUIRED LATCH SIDE FOR SIDE CLEARANCE. SEE |
| | FIGURE 404.2.4.1.(A) A REQUIRED 18 INCHES ON THE LATCH |
| | SIDE OF THE DOORWAY. |
| | |
| | 2B) THE EXISTING RESTROOM, ROOM NUMBER 315 DOES NOT |
| | COMPLY WITH THE RESTROOM REQUIREMENTS. IN THE 2017 |
| | FBC-PLUMBING CODE REVIEW SECTION 403.3.3 WHERE |
| | ACCESSIBLE RESTROOMS ARE EITHER ONE STORY ABOVE OR |
| | BELOW THE SPACE REQUIRED TO BE PROVIDED WITH TOILET |
| | FACILITIES SHALL NOT EXCEED A DISTANCE OF 500 FT. IF |
| | THE EXISTING RESTROOM QUALIFIES THEN SIGNAGE WOULD BE |
| | REQUIRED WHERE THE ACCESSIBLE RESTROOMS ARE LOCATED. |
| | SEE ACCESSIBILITY CODE SECTION 703.1. IF THE ACCESSIBLE |
| | RESTROOMS ARE OVER THE ALLOWABLE TRAVEL DISTANCE THEN |
| | THE DOLLARS AMOUNT FOR ACCESSIBLE UPGRADES TO THE |
| | RESTROOM WOULD BE INCLUDED. PLEASE NOTE IF THE DOLLAR |
| | AMOUNT EXCEEDS THE $14,000.00 DOLLARS YOU WOULD TAKE |
| | THE VARIOUS ITEMS WITHIN THE EXISTING BATHROOM WHERE UP |
| | TO $14,000.00 IS TO BE SPENT. THIS WOULD BE ADDED TO |
| | THE OTHER ITEMS (EXISTING DOORS) FOR YOUR LETTER FOR |
| | DISPROPORTIONATE COST. |
| | |
| | 2C) ANOTHER ITEM THAT SHOWS ON THE FLOOR PLAN IS AN |
| | EXISTING PASS-THROUGH CHECK-IN AND CHECK-OUT COUNTER. |
| | CHECK WRITING SURFACES. 904.3.3. CHECK WRITING |
| | SURFACES. WHERE PROVIDED, CHECK WRITING SURFACES SHALL |
| | COMPLY WITH 902.3. /902.3 HEIGHT. THE TOPS OF DINING |
| | SURFACES AND WORK SURFACES SHALL BE 28 INCHES MINIMUM |
| | AND 34 INCHES MAXIMUM ABOVE THE FINISH FLOOR OR GROUND. |
| | |
| | 3) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION |
| | & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |