| 2020-03-04 11:36:44 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| | MARSHAL, WITH THE FOLLOWING COMMENTS: |
| | |
| | |
| | 1) THE SUBMITTED PLANS INDICATED A LIMITED FIRE ALARM |
| | SYSTEM THAT IS NOT CODE COMPLINAT. |
| | |
| | PER NFPA 101, CH 32 NEW RESIDENTIAL BOARD AND CARE |
| | OCCUPANCIES |
| | |
| | 33.2.3.4 DETECTION, ALARM, AND COMMUNICATIONS SYSTEMS. |
| | 33.2.3.4.1 FIRE ALARM SYSTEMS. A MANUAL FIRE ALARM |
| | SYSTEM SHALL |
| | BE PROVIDED IN ACCORDANCE WITH SECTION 9.6, UNLESS THE |
| | PROVISIONS |
| | OF 33.2.3.4.1.1 OR 33.2.3.4.1.2 ARE MET. |
| | 33.2.3.4.1.1 A FIRE ALARM SYSTEM SHALL NOT BE REQUIRED |
| | WHERE |
| | INTERCONNECTED SMOKE ALARMS COMPLYING WITH 33.2.3.4.3 |
| | AND NOT |
| | LESS THAN ONE MANUAL FIRE ALARM BOX PER FLOOR ARRANGED |
| | TO |
| | CONTINUOUSLY SOUND THE SMOKE DETECTOR ALARMS ARE |
| | PROVIDED. |
| | 33.2.3.4.1.2 OTHER MANUALLY ACTIVATED CONTINUOUSLY |
| | SOUNDING |
| | ALARMS ACCEPTABLE TO THE AUTHORITY HAVING JURISDICTION |
| | SHALL BE |
| | PERMITTED IN LIEU OF A FIRE ALARM SYSTEM. |
| | 33.2.3.4.2 OCCUPANT NOTIFICATION. OCCUPANT NOTIFICATION |
| | SHALL BE |
| | IN ACCORDANCE WITH 9.6.3. |
| | |
| | PLEASE REVIEW AND CORRECT OR JUSTIFY WITH SPECIFIC |
| | DETAILS IN A WRITTEN NARRATIVE. |
| | |
| | |
| | 2) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET |
| | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE |
| | ABOVE. |
| | |
| | |
| | |
| | 3) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE |
| | RE-SUBMITTAL OF THE ABOVE. |
| | |
| | |
| | |
| | |
| | PETER LEDUC |
| | FIRE MARSHAL |