Plan Review Notes
Plan Review Notes For Permit 20020821
Permit Number 20020821
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2020-03-04 11:36:44THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) THE SUBMITTED PLANS INDICATED A LIMITED FIRE ALARM
 SYSTEM THAT IS NOT CODE COMPLINAT.
  
 PER NFPA 101, CH 32 NEW RESIDENTIAL BOARD AND CARE
 OCCUPANCIES
  
 33.2.3.4 DETECTION, ALARM, AND COMMUNICATIONS SYSTEMS.
 33.2.3.4.1 FIRE ALARM SYSTEMS. A MANUAL FIRE ALARM
 SYSTEM SHALL
 BE PROVIDED IN ACCORDANCE WITH SECTION 9.6, UNLESS THE
 PROVISIONS
 OF 33.2.3.4.1.1 OR 33.2.3.4.1.2 ARE MET.
 33.2.3.4.1.1 A FIRE ALARM SYSTEM SHALL NOT BE REQUIRED
 WHERE
 INTERCONNECTED SMOKE ALARMS COMPLYING WITH 33.2.3.4.3
 AND NOT
 LESS THAN ONE MANUAL FIRE ALARM BOX PER FLOOR ARRANGED
 TO
 CONTINUOUSLY SOUND THE SMOKE DETECTOR ALARMS ARE
 PROVIDED.
 33.2.3.4.1.2 OTHER MANUALLY ACTIVATED CONTINUOUSLY
 SOUNDING
 ALARMS ACCEPTABLE TO THE AUTHORITY HAVING JURISDICTION
 SHALL BE
 PERMITTED IN LIEU OF A FIRE ALARM SYSTEM.
 33.2.3.4.2 OCCUPANT NOTIFICATION. OCCUPANT NOTIFICATION
 SHALL BE
 IN ACCORDANCE WITH 9.6.3.
  
 PLEASE REVIEW AND CORRECT OR JUSTIFY WITH SPECIFIC
 DETAILS IN A WRITTEN NARRATIVE.
  
  
 2) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
  
 3) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
  
  
 PETER LEDUC