Plan Review Notes
Plan Review Notes For Permit 20020821
Permit Number 20020821
Review Stop B
Sequence Number 1
Notes
Date Text
2020-03-11 12:43:33CHANGE OF OCCUPANCY FBC EXISTING BUILDING 1001.2
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
  
 CORRECTIONS NEEDED -
 1) GROUP HOME IS A CHANGE OF OCCUPANCY FROM A SINGLE
 FAMILY HOUSE. FBC EXISTING BUILDING 1012
 2) PLEASE SHOW THE OCCUPANCY CLASSIFICATION PER FBC
 CHAPTER 3
 3) GROUP HOME FALLS UNDER FBC 310.6 (R-4) - SHOW THE
 REQUIRED SPRINKLER SYSTEM PER FBC 903.2.8
 4) SHOW WHICH APPLIES - - CONDITION 1 OR 2 - - - PER
 FBC 310.6.1
 5) PLEASE SHOW THE OCCUPANT LOAD PER FBC 1004
 6) PLEASE SHOW THE MEANS OF EGRESS - EXIT DOOR SIZES
 AND LOCATIONS. FBC EXISTING BUILDING 1012.4
 7) PLEASE FILL OUT A BUILDING PERMIT APPLICATION (CHECK
 "STRUCTURAL") FOR THE CHANGE OF OCCUPANCY - SHOW IN THE
 "FURTHER WORK DESCRIPTION" ON THE PERMIT APPLICATION
 "CHANGE OF OCCUPANCY FROM ____ TO ___".
 8) PLEASE SHOW SEPARATION WALLS TO COMPLY WITH FBC 420
  