| Notes |
| Date |
Text |
| 2020-02-24 16:57:55 | WALL OPENING - FBC 107.3.5 | | | REVIEWED BY ROGER MCPHERSON | | | 561-805-6716 | | | [email protected] | | | | | | CORRECTIONS NEEDED - | | | 1) PLEASE PROVIDE A FLOOR PLAN SHOWING THE LOCATION OF | | | THE WORK. FBC WPB AMENDMENTS 107.3.5 | | | 2) DRAWINGS SHOW DIFFERENT STEEL BEAM LENGHTS - ROOF | | | PLAN SHOWS 1' 6" OPENING OVERHANG EACH END WITH 10' | | | OPENING - SECTION SHOWS A 12' 8" BEAM - PLEASE CLARIFY. | | | 3) IS THE WALL FIRE RATED ? FBC 601 SHOULD THE ADDED | | | STEEL BE PROTECTED ? | | | 4) DRAWING SHOULD SHOW THE BUILDING CONSTRUCTION TYPE | | | PER FBC CHAPTER 6 | | | 5) PLEASE SHOW THE OCCUPANCY CLASSIFICATION PER FBC | | | CHAPTER 3 | | | |
|