| 2020-05-08 14:56:01 | 3RD REVIEW FBC-2017 MECHANICAL |
| | PERMIT #20020745 |
| | 5/8/20 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| | 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) I WAS NOT ABLE TO LOCATE THE PREVIOUSLY SUBMITTED AC |
| | CALCULATIONS. PLEASE RE-SUBMIT THE CALCULATIONS OR |
| | PROVIDE NEW CALCULATIONS FOR THE SYSTEMS- SECTION |
| | C403.2.1 FBC EC. |
| | |
| | PLEASE UPDATE AND UPLOAD CORRECTED PLAN SHEETS TO |
| | ADDRESS THE COMMENTS FROM THE 1ST REVIEW LISTED BELOW. |
| | |
| | 1) SHEET M-101: AIR HANDLERS ARE NOT ALLOWED IN THE |
| | ATTICS OF COMMERCIAL BUILDINGS- SECTION C403.2.9.6 FBC |
| | EC. THE UNITS WILL HAVE TO BE RELOCATED. |
| | SHEET M101: THE ARCHITECT'S RESPONSE THAT THE SPACE |
| | ABOVE THE CEILING IS NOT AN ATTIC BY DEFINITION IS |
| | ACCEPTED, HOWEVER THE ENGINEER OF RECORD HAS NOT |
| | REMOVED OR CORRECTED KEY NOTES #8, 9, 11, & 12 WHICH |
| | IDENTIFY THE SPACE AS AN ATTIC. |
| | |
| | 6) PROVIDE MINIMUM VENTILATION CALCULATIONS FOR ALL |
| | ROOMS AND SPACES PER TABLE 403.3.1.1 FBC ML. PROVIDE A |
| | SCHEDULE ON THE PLAN THAT INDICATES THE REQUIRED AND |
| | PROVIDED CFMS OF OUTDOOR AIR. |
| | THE VENTILATION CALCULATIONS ON SHEET M-101 CAN NOT BE |
| | CHECKED FOR COMPLIANCE WITH TABLE 403.3.1.1 FBC M |
| | BECAUSE THEY DO NOT INDICATE THE REQUIRED CFMS PER |
| | PERSON AND CFMS PER SQ. FT. OF THE ROOMS OR SPACES. |
| | PLEASE PROVIDE A COMPLETE CALCULATION TABLE. |
| | |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |
| | CHRISTOPHER L. COLE |
| | MECHANICAL PLANS EXAMINER |
| | 401 CLEMATIS STREET |
| | WEST PALM BEACH FL 33401 |
| | 561-805-6719 |
| | [email protected] |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |
| | CHRISTOPHER L. COLE |
| | MECHANICAL PLANS EXAMINER |
| | 401 CLEMATIS STREET |
| | WEST PALM BEACH FL 33401 |
| | 561-805-6719 |
| | [email protected] |
| | |