| 2020-04-14 10:57:42 | 1) SHT. A-411 & SHT. A-102 - DETAIL #1 - SHOW THE CLEAR |
| | FLOOR SPACE FOR THE HANDICAP ACCESSIBLE WATER CLOSETS |
| | ON THE ENLARGED FLOOR PLANS. COMPLY WITH 2017 |
| | FBC-ACCESS. SEC. 604.3. SHOW THE LENGTH AND WIDTH |
| | DIMENSIONS OF THE CLEAR FLOOR SPACE ON THE PLANS.THE |
| | ONLY CLEAR FLOOR SPACE SHOWN IS FOR THE LAVATORY. 2ND |
| | REQUEST. |
| | 2) SHT. A-102 - WOMEN'S AND MEN'S RESTROOMS #115 & 116 |
| | - A LAVATORY IS REQUIRED IN THE ACCESSIBLE TOILET |
| | STALLS PER 2017 FBC-ACCESS.SEC. 604.8.1.6. 2ND REQUEST. |
| | 3) SHT. A-102 - MEN'S & WOMEN'S RESTROOMS #115 & #116 - |
| | THE DOORSIN THE HANDICAP ACCESSIBLE TOILET STALLS SHALL |
| | BE LOCATED IN THE FRONT PARTITION OR IN THE SIDE WALL |
| | OR PARTITION FARTHEST FROM THE WATER CLOSET, NOT |
| | LOCATED DIRECTLY IN FRONT OF THE WATER CLOSET.2017 FBC- |
| | ACCESS. SEC.604.8.1.2. 2ND REQUEST. |
| | 4) THE WATER COOLER LOCATED ON THE EAST WALL OF THE |
| | RESTROOM FACILITY SHALL BE A HI-LO UNIT OR 2 SEPARATE |
| | UNITS COMPLYING WITH THE FBC-ACCESS. SEC. 211.1 & |
| | FBC-PLUMBING SEC.410.3. THIS WAS OVERLOOKED ON THE |
| | PREVIOUS REVIEW. |
| | 5) SHT. A-401 - VERTICAL GRAB BARS ARE SHOWN IN THE |
| | ACCESSIBILITY DETAILS. SEC. 609.4 OF THE FBC-ACCESS. |
| | STATES THAT GRAB BARS SHALL BE INSTALLED IN THE |
| | HORIZONTAL POSITION.THERE IS NO EXCEPTION IN THE |
| | ACCESSIBILITY CODE ALLOWING GRAB BARS TO BE INSTALLED |
| | IN A VERTICAL POSITION EVEN THOUGH THEY ARE NOT |
| | "REQUIRED" GRAB BARS. |
| | 6) SHT. P-601 - WATER HEATER SCHEDULE - IN THE "NOTES" |
| | COLUMN REFERENCE IS MADE TO NUMBERED NOTES BUT THERE |
| | ARE NO NUMBERED NOTES SHOWN. CLARIFY. |
| | |
| | TIM LARGE |
| | CHIEF PLUMBING INSPECTOR |
| | PLUMBING PLAN REVIEW |