| Plan Review Notes For Permit 20020745 |
| Permit Number |
20020745 |
|
| Review Stop |
B |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2020-04-13 16:41:07 | NEW BUILDING | | | REVIEWED BY ROGER MCPHERSON | | | 561-805-6716 | | | [email protected]. | | | | | | CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107 | | | 1) SURVEY NEEDS TO BE ELECTRONICALLY SIGNED BY THE | | | SURVEYOR. (DOES NOT SHOW IN "ADOBE" AS ELECTRONICALLY | | | SIGNED. | | | 2) PLEASE SHOW THE FLOOD ZONE PER THE LATEST FIRM. | | | 3) ELECTRONIC SIGNATURE ON THE STRUCTURAL DRAWINGS | | | NEEDS TO BE VERIFIED BY A CERTIFICATION AUTHORITY - SEE | | | 61G15-23.004(2). | | | 4) PLEASE PROVIDE A SIGNED AND SEALED SOIL REPORT. | | | 5) PLEASE SHOW THE REQUIRED HANDRAILING AT THE STAIRS ( | | | HEIGHT, EXTENSIONS AND ONE ON EACH SIDE) TO COMPLY WITH | | | FBC 1014. | | | 6) PLEASE SHOW TERMITE TREATMENT REQUIRED TO COMPLY | | | WITH FBC 1816. | | | 7) PLEASE PROVIDE SIDING ATTACHMENT DETAILS OR PRODUCT | | | APPROVALS. | | | 8) PLEASE PROVIDE SOLAR PANEL ATTACHMENT DETAILS OR | | | PRODUCT APPROVALS. | | | 9) PLEASE SHOW THE REQUIRED NAILING FOR THE STRAPPING | | | (SIZE OF NAIL OR SCREW AND AMOUNT). | | | 10) PLEASE PROVIDE THE PRODUCT APPROVAL FOR THE METAL | | | ROOFING. | | | 11) ANY DEFERRALS PLEASE PUT IN WRITING. | | | |
|