Text |
| 2020-03-13 12:29:47 | 1) SHOW THE CLEAR INSIDE DIMENSIONS (L X W) FOR THE |
| | ACCESSIBLE TOILET STALLS AND TOILET ROOMS ON THE |
| | ENLARGED FLOOR PLANS. , WPB AMEND. TO FBC SEC. 107.2.1. |
| | 2) SHOW THE CLEAR FLOOR SPACE FOR THE HANDICAP |
| | ACCESSIBLE WATER CLOSETS ON THE ENLARGED FLOOR PLANS. |
| | COMPLY WITH 2017 FBC-ACCESS. SEC. 604.3. SHOW THE |
| | LENGTH AND WIDTH DIMENSIONS OF THE CLEAR FLOOR SPACE ON |
| | THE PLANS. |
| | 3) SHT.A102 - WOMEN'S AND MEN'S RESTROOMS #115 & 116 - |
| | A LAVATORY IS REQUIRED IN THE ACCESSIBLE TOILET STALL |
| | PER 2017 FBC-ACCESS. SEC.604.8.1.6. SHOW THIS ON ALL |
| | APPLICABLE PLANS. |
| | 4) SHT. A101 - THE TOILET ROOMS IN THE TENNIS CENTER |
| | ARE LABELED AS UNISEX.THE TOILET ROOMS SHALL BE LABELED |
| | AS GENDER SPECIFIC PER 2017 FBC-PLUMBING SEC.403.2. |
| | 5) SHT. A401 - ALL GRAB BARS SHALL BE MEASURED FROM THE |
| | FINISH FLOOR TO THE TOP OF THE GRIPPING SURFACE PER |
| | 2017 FBC-ACCESS. SEC.609.4. |
| | 6) SHOW THE CLEAR INSIDE DIMENSIONS (L X W) OF ALL THE |
| | SHOWERS. WPB AMEND. TO FBC . SEC.107.2.1. |
| | 7) SUBMIT AN ENLARGED FLOOR FLOOR PLAN FOR THE MEN'S |
| | TOILET ROOM IN THE RESTROOM FACILITY.WPB AMEND. TO FBC |
| | SEC. 107.2.1. |
| | 8) A BACKFLOW PREVENTION DEVCE IS REQUIRED ON THE WATER |
| | SERVICE FOR THE TENNIS CENTER AND THE RESTROOM FACILITY |
| | PER THE CITY OF WEST PALM BEACH CROSS CONNECTION |
| | CONTROL MANUAL.. A SEPARATE PERMIT IS REQUIRED FOR THE |
| | BACKFLOW DEVICES. |
| | 9) SUBMIT MANUFACTURER'S SPECIFICATIONS AND SHOP |
| | DRAWINGS FOR THE RAINWATER COLLECTION SYSTEM. WPB |
| | AMEND. TO FBC SEC. 107.2.1. |
| | 10) NONPOTABLE WATER SYSTEMS SHALL BE IDENTIFIED IN |
| | ACCORDANCE WITH 2017 FBC-PLUMBING SECS.608.8 - |
| | 608.8.2.3. |
| | 11) SHT. P104 - DETAIL # 1- RESTROOM FACILITY - THE 3/4 |
| | INCH CW LINES HAS A NOTE THAT READS" SEE 1/P101 FOR |
| | CONTINUATION". SHT. P101 IS FOR THE TENNIS CENTER AND |
| | THE LINE IS NOT SHOWN. CLARIFY. |
| | 12) SHT. P104 - DETAIL #1 - THE WATER RISER SHOWS A 2 |
| | INCH NPW BY FIXTURES P3, P7 & IM LINE TO NOWHERE. |
| | CLARIFY. |
| | 13) SHT.P104 - THERE IS AN NPW LINE BY THE 1 1/2 NPW |
| | LINE TO P1A THAT HAS NO SIZE AND GOES NOWHERE. CLARIFY. |
| | 14) SUBMIT MANUFACTURER'S SPECIFICATIONS AND |
| | INSTALLATION MANUAL FOR THE FILTRATION SKID. WPB AMEND. |
| | TO FBC SEC. 107.2.1. |
| | 15) BACK TO BACK WATER CLOSET CONNECTIONS SHALL COMPLY |
| | WITH 2017 FBC-PLUMBING SEC. 706.3 (EXCEPTION). SHOW |
| | COMPLIANCE ON PLANS. |
| | 16) SHT. P105 - DETAIL #1 SHOWS SANITARY TEES USED IN |
| | THE HORIZONTAL POSITION WHICH IS NOT PERMITTED PER 2017 |
| | FBC-PLUMBING TABLE 706.3. ALSO, THE PIPING TO FIXTURE |
| | P3 IS S- TRAPPED. |
| | 17) SHT. P501 - THE T & P LINE FOR THE WATER HEATER |
| | SHALL DISCHARGE THROUGH AN AIR GAP LOCATED IN THE SAME |
| | ROOM AS THE WATER HEATER. 2017 FBC-PLUMBING SEC.504.6. |
| | 18) SUBMIT THE MANUFACTURER'S SPECIFICATIONS FOR THE |
| | WATTS ES-LSMMV-M1. DEVICES USED FOR TEMPERING WATER |
| | SHALL CONFORM TO ASSE 1070 PER 2017 FBC-PLUMBING SEC. |
| | 607.1.2. |
| | 19) AS OF APRIL 16, 2015 THE MINIMUM ENERGY FACTOR FOR |
| | THE 10 GALLON STORAGE WATER HEATER IS .95 PER 10 CFR |
| | 430.32. THE ENERGY FACTOR FOR THE 66 GALLON STORAGE |
| | WATER HEATER SHALL BE 1.98. SHOW THESE CHANGES ON THE |
| | ENERGY CALCULATIONS. |
| | 20) THE GRAB BARS IN THE ACCESSIBLE SHOWERS SHALL BE |
| | INSTALLED 6 INCHES MAXIMUM FROM ADJACENT WALLS. 2017 |
| | FBC-ACCESS. SEC.608.3.2. |
| | 21)THE CONTROLS IN THE ACCESSIBLE SHOWERS SHALL BE |
| | LOCATED 27 INCHES MAXIMUM FROM THE SEAT WALL. SHOW THIS |
| | ON THE FLOOR PLANS. 2017 FBC-ACCESS. SEC. 608.5.2. |
| | 22) THE DOORS IN THE HANDICAP ACCESSIBLE TOILET STALLS |
| | SHALL BE LOCATED IN THE FRONT PARTITION OR IN THE SIDE |
| | WALL OR PARTITION FARTHEST FROM THE WATER CLOSET, NOT |
| | LOCATED DIRECTLY IN FRONT OF THE WATER CLOSET.. 2017 |
| | FBC_ ACCESS. SEC.604.8.1.2. |
| | 23) SHT. P104 - DETAIL #1 - THE 3/4 INCH NPW LINE IS |
| | ALSO NOTED AS "CW". CLARIFY. |
| | |
| | TIM LARGE |
| | CHIEF PLUMBING INSPECTOR |
| | PLUMBING PLAN REVIEW |
| | 561-805-6692 |