| 2020-03-11 15:35:10 | 1ST REVIEW FBC-2017 MECHANICAL |
| | PERMIT #20020745 |
| | 3/11/20 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| | 2017 |
| | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH |
| | EDITION 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) SHEET M-101: AIR HANDLERS ARE NOT ALLOWED IN THE |
| | ATTICS OF COMMERCIAL BUILDINGS- SECTION C403.2.9.6 FBC |
| | EC. THE UNITS WILL HAVE TO BE RELOCATED. |
| | |
| | 2 )M-101: PLEASE NOTE THAT AUTOMATIC SHUTOFF DAMPERS, |
| | EITHER MOTORIZED OR GRAVITY, WILL BE REQUIRED FOR THE |
| | O/A INTAKES TO THE RELOCATED AIR HANDLERS- SECTION |
| | C403.2.4.3 FBC EC. |
| | |
| | 3) M-101: PROVIDE A DUCT SMOKE DETECTOR IN THE SUPPLY |
| | SYSTEM OF AHU-2 PER SECTION 606.2.1 FBC M. PLEASE NOTE |
| | THAT AN EXEMPTION CAN BE APPLIED IF THE MANUFACTURER'S |
| | PERFORMANCE DATA INDICATES THE AIR HANDLER IS NOT |
| | CAPABLE OF PRODUCING OVER 2000 CFMS OF SUPPLY AIR. |
| | |
| | 4) SUBMIT AC COOLING AND HEATING CALCULATIONS FOR THE |
| | NEW SYSTEMS- SECTION C403.2.1 FBC EC. |
| | |
| | 5) SUBMIT AN ENERGY COMPLIANCE REPORT FOR THE NEW |
| | TENNIS CENTER- SEE SECTIONS C101.5 AND C401.2 FBC EC |
| | FOR COMPLIANCE AND SUBMITTAL INFORMATION. |
| | |
| | 6) PROVIDE MINIMUM VENTILATION CALCULATIONS FOR ALL |
| | ROOMS AND SPACES PER TABLE 403.3.1.1 FBC ML. PROVIDE A |
| | SCHEDULE ON THE PLAN THAT INDICATES THE REQUIRED AND |
| | PROVIDED CFMS OF OUTDOOR AIR. |
| | |
| | 7) PROVIDE A CONDENSATE DISPOSAL PLAN- SECTION 307.2.1 |
| | FBC M. |
| | |
| | 8) PROVIDE ENGINEERING FOR INSTALLATION OF THE |
| | CONDENSER PAD AND MOUNTING OF THE CONDENSERS- SECTION |
| | 301.15 FBC M. |
| | |
| | 9) A-152 & A-203: A) A MINIMUM 30 INCHES DEEP AND 30 |
| | INCHES WIDE LEVEL PLATFORM WITH 42" HIGH GUARD RAILS |
| | SHALL BE PROVIDED FOR SERVICE AND REPLACEMENT OF THE |
| | ROOFTOP EXHAUST FANS- SECTION 306.5.1 FBC M. B) A |
| | RECEPTACLE OUTLET SAHLL BE POVIDED AT OR NEAR THE FANS |
| | IN ACCORDANCE WITH NFPA 70- SECTION 306.5.2 FBC M. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD |
| | SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER |
| | SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN |
| | THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS |
| | PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS |
| | PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR |
| | UPDATED. |
| | |