| 2020-02-25 14:01:36 | WINDOWS | | | REVIEWED BY ROGER MCPHERSON | | | 561-805-6716 | | | [email protected] | | | | | | CORRECTIONS NEEDED - | | | 1) PLEASE PROVIDE A FLOOR PLAN SHOWING EACH WINDOW | | | LOCATION AND SIZE. PLEASE INDICATE IF YOU ARE REPLACING | | | EXISTING WINDOWS OR CREATING A NEW OPENING. (WHICH WILL | | | REQUIRE ADDITIONAL SIGNED AND SEALED OPENING DETAILS | | | FROM AN ARCHITECT OR ENGINEER FBC 1609.1). | | | 2) FOR THE WINDOWS IN THE CORNER OF THE BUILDING - | | | PLEASE SHOW THE DISTANCE FROM THE EDGE OF THE WINDOW TO | | | THE EDGE OF THE BUILDING. (NEEDED TO DETERMINE IF THE | | | WINDOW IS IN WIND ZONE 4 OR 5.) | | | 3) PRODUCT APPROVAL PROVIDED FOR THE ALUMINUM SLIDING | | | GLASS DOOR IS ONLY GOOD FOR "SMALL MISSILE IMPACT". | | | GLAZING BELOW 30 FEET OF GRADE IS REQUIRED TO MEET | | | "LARGE MISSILE IMPACT" FBC 1609.1.2 | | | 4) PLEASE PROVIDE 2 COPIES OF EACH DRAWING, DOCUMENT, | | | OR PRODUCT APPROVAL. | | | |
|