Plan Review Notes
Plan Review Notes For Permit 20020686
Permit Number 20020686
Review Stop E
Sequence Number 1
Notes
Date Text
2020-03-25 16:24:12 
 JAKE LEAHY
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 1) PLANS NOT SIGNED
  
 2) PAGE E-15 RISER SHOWS A #4 CONDUCTOR ON A 150A FUSE.
  
 3) FAULT CURRENT CALCULATION PER 110.24 FOR THE SERVICE