| Date |
Text |
| 2020-05-08 14:33:24 | 2ND REVIEW FBC-2017 MECHANICAL |
| | PERMIT #20020669 |
| | 5/8/20 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH |
| | EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED |
| | |
| | 1) SHEETS M1 & M2: THE MECHANICAL PLANS ARE OLDER |
| | VERSIONS AND SHOULD BE UPDATED TO MATCH THE OTHER NEW |
| | PLANS FOR THE MODELS- SECTION 107.2.1 WPB. PLEASE NOTE |
| | THE CONDENSER LOCATIONS AT THE REAR OF EACH TOWNHOUSE |
| | AS SHOWN ON SHEET M4.6 SHOWING ARE APPROVED LOCATIONS. |
| | |
| | 2) SHEET M1, NAVARRE MODEL: |
| | A) IT APPEARS THAT FLEX DUCTS WILL BE INSTALLED IN THE |
| | GARAGE. PLEASE PLACE A NOTE TO VERIFY THE DUCTS WILL BE |
| | INSTALLED ABOVE THE REQUIRED DRYWALL CEILING- SECTION |
| | R302.5.2 FBC RES |
| | B) THE MAIN RETURN TO THE AC CLOSET IS SLIGHTLY |
| | UNDERSIZED- 50 SQ. INCHES PER 100 CFMS REQUIRED. A |
| | 24X24 GRILL WILL BE ADEQUATE. |
| | |
| | 3) REVISE THE SURVEY TO SHOW CORRECT TOWNHOUSE AND LOT |
| | LOCATIONS- SECTION 107.2.1 WPB. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. ADDITIONALLY, |
| | |
| | CHRISTOPHER L. COLE |
| | MECHANICAL PLANS EXAMINER |
| | 401 CLEMATIS STREET |
| | WEST PALM BEACH FL 33401 |
| | 561-805-6719 |
| | [email protected] |