| | 2ND REVIEW FBC-2017 MECHANICAL |
| | PERMIT #20020654 |
| | 5/8/2020 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH |
| | EDITION 2017 |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| | 2017 |
| | FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) SHEET M4.6: THE REVISED SHEET SHOWS UNDERSLAB |
| | REFRIGERANT PIPING RUNS CROSSING THE INDIVIDUAL |
| | PROPERTY LINES OF THE TOWNHOUSES. PLEASE SEE SECTION |
| | R302.2 FBC RES AND RELOCATE THE CONDENSERS BACK TO |
| | THEIR ORIGINAL LOCATIONS AT THE REAR OF EACH TOWNHOUSE. |
| | |
| | 2) THE 421 18TH ST. ADDRESS ON THE AC CALCULATIONS DOES |
| | NOT MATCH THE ADDRESSES ON THE PERMIT APPLICATION AND |
| | THE ENERGY CALCS. PLEASE PROVIDE CALCULATIONS |
| | SPECIFICALLY FOR THE PROPOSED TOWNHOUSE- SECTION |
| | R403.7.1 FBC EC. REVISE THE SURVEY TO SHOW CORRECT |
| | TOWNHOUSE AND LOT LOCATIONS- SECTION 107.2.1 WPB. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |