| Plan Review Notes For Permit 20020645 |
| Permit Number |
20020645 |
|
| Review Stop |
M |
| Sequence Number |
4 |
|
| Notes |
| Date |
Text |
| 2021-02-22 07:19:40 | SHEET M4.6 IS STILL SHOWING THE REFRIGERATE LINES | | | RUNNING UNDER SLAB TO THE SIDE OF THE BUILDING. THE | | | REFRIGERATE LINES CANNOT RUN UNDER THE SLAB UNDER | | | OTHERS PROPERTY. PLEASE SHOW THE CONDENSING UNIT FOR | | | EACH TOWNHOME AT THE REAR OF THE BUILDING AND BETWEEN | | | THE PROPERTY LINES OF ITS OWN PROPERTY. FBC RES R302.2 | | | | | | MICHAEL EDWARDS | | | MECHANICAL EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL. 33401 | | | 561-805-6728 | | | [email protected] | | | |
|