| Plan Review Notes For Permit 20020635 |
| Permit Number |
20020635 |
|
| Review Stop |
B |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2020-08-25 13:10:52 | REMODEL | | | REVIEWED BY ROGER MCPHERSON | | | 561-805-6716 | | | E MAIL = [email protected] | | | CODE USED FOR REVIEW - 2017 FBC WITH WPB CHAPTER 1 | | | AMENDMENTS | | | | | | 2ND REVIEW - SORRY FOR THE DELAY - NOW THAT THIS REVIEW | | | IS ELECTRONIC THE RE REVIEWS WILL BE FASTER - PLEASE | | | EMAIL ME WHEN THE RE REVIEW IS SUBMITTED SO WE HAVE NO | | | MORE DELAYS. | | | | | | CORRECTIONS NEEDED - | | | 1) PLEASE PROVIDE COMPLETE MIAMI DADE OR FLORIDA STATE | | | PRODUCT APPROVALS FOR THE NEW EXTERIOR DOORS. ALL | | | PRODUCT APPROVALS IF NOT LISTED ON THE DRAWINGS NEED TO | | | BE REVIEWED AND MARKED APPROVED BY THE BUILDING | | | DESIGNER OF RECORD. FBC WPB AMENDMENTS 107.3.5 | | | 2) PLEASE PROVIDE STRUCTURAL EXTERIOR WALL DETAILS FOR | | | THE NEW DOOR OPENING AT THE FAMILY ROOM. SHOW ALL | | | FRAMING, HURRICANE STRAPPING, ALL ATTACHMENTS ETC.. FOR | | | THE EXTERIOR WALL FRAMING. FBC WPB AMENDMENTS 107.2.4 | | | 3) NEED TO SHOW THE WINDOW SIZES. | | | 4) PLEASE ADD A SMOKE DETECTOR TO BEDROOM NUMBER 3 - | | | FBC R314.2.2 | | | | | | |
|