| Plan Review Notes For Permit 20020635 |
| Permit Number |
20020635 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2020-02-21 16:22:39 | REMODEL | | | REVIEWED BY ROGER MCPHERSON | | | 561-805-6716 | | | [email protected] | | | | | | CORRECTIONS NEEDED - | | | 1) APPLICATION "WORK DESCRIPTION" DOES NOT MATCH THE | | | DRAWINGS PROVIDED - INTERIOR WALLS,EXTERIOR WALLS (NEW | | | OPENINGS ETC.) NEW EXTERIOR DOORS. PLEASE REVISE THE | | | BUILDING PERMIT APPLICATION "WORK DESCRIPTION". FBC WPB | | | AMENDMENTS 105 | | | 2) CONTRACT FOR WORK SHOWN ON THE DRAWINGS PROVIDED | | | DOES NOT INCLUDE THE EXTERIOR WALL REPAIR AT NEW | | | OPENINGS, INTERIOR WALLS AND NEW EXTERIOR DOORS. PLEASE | | | REVISE THE BUILDING PERMIT APPLICATION FOR THE JOB | | | "VALUE". FBC WPB AMENDMENTS 105 | | | 3) PLEASE PROVIDE COMPLETE MIAMI DADE OR FLORIDA STATE | | | PRODUCT APPROVALS FOR THE NEW EXTERIOR DOORS. ALL | | | PRODUCT APPROVALS IF NOT LISTED ON THE DRAWINGS NEED TO | | | BE REVIEWED AND MARKED APPROVED BY THE BUILDING | | | DESIGNER OF RECORD. FBC WPB AMENDMENTS 107.3.5 | | | 4) PLEASE PROVIDE STRUCTURAL EXTERIOR WALL DETAILS FOR | | | THE NEW DOOR OPENING AT THE FAMILY ROOM AND WATER | | | HEATER. SHOW ALL FRAMING, HURRICANE STRAPPING, ALL | | | ATTACHMENTS ETC.. FBC WPB AMENDMENTS 107.2.4 | | | 5) PLEASE SHOW THE WIND LOAD DESIGN CRITERIA PER FBC | | | R301.2.1 - FBC BUILDING 1603.1.4 (WIND SPEED,WIND | | | EXPOSURE, DESIGN PRESSURES FOR THE NEW EXTERIOR DOOR | | | OPENINGS) | | | | | | PLANS RETURNED TO BIN R22 | | | | | | |
|