| Notes |
| Date |
Text |
| 2020-03-04 13:56:52 | 1) SHOW THE RECIRCULATING LINE ON THE WATER RISER | | | DIAGRAM IN ITS ENTIRETY. WPB AMEND. TO FBC SEC.107.2.1. | | | 2) SANITARY VENTS EXCEEDING 40 FEET IN DEVELOPED LENGTH | | | SHALL BE INCREASED BY ONE NOMINAL PIPE SIZE FOR THE | | | ENTIRE DEVELOPED LENGTH OF THE VENT PIPE PER 2017 | | | FBC-PLUMBING SE. 906.2. THE SUBMITTED NARRATIVE | | | RESPONSE STATES TO REFER TO SHT. P-5.THIS SHEET IS THE | | | WATER RISER NOT THE SANITARY RISER AND THE SANITARY | | | RISER ON P-4 HAS NOT BEEN REVISED. 2ND REQUEST. | | | 3) PROVIDE A KEYNOTE LEGEND FOR THE KEYNOTE NUMBERS | | | SHOWN ON THE WATER HEATER DETAIL ON SHT. P-6. | | | | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | PLUMBING PLAN REVIEW | | | 561-805-6692 | | | [email protected] | | | |
|