Plan Review Notes
Plan Review Notes For Permit 20020614
Permit Number 20020614
Review Stop P
Sequence Number 1
Notes
Date Text
2020-02-24 09:15:351) A HOT WATER RECIRCULATING LINE IS REQUIRED PER 2017
 FBC - PLUMBING SEC. 607.2.
 2) SANITARY VENTS EXCEEDING 40 FEET IN DEVELOPED LENGTH
 SHALL BE INCREASED BY ONE NOMINAL PIPE SIZE FOR THE
 ENTIRE DEVELOPED LENGTH OF THE VENT PIPE PER 2017
 FBC-PLUMBING SE. 906.2.
 3) THE SINK BY TOILET ROOM #232 IS LABELED S-3 ON THE
 SANITARY RISER AND S-1 ON THE WATER RISER. CLARIFY.
 4) THE SINK IN THE LAB/PHLEBOTOMY ROOM #227 IS LABELED
 AS S-1 ON THE SANITARY RISER AND S-2 ON THE WATER
 RISER. CLARIFY.
 5) SUBMIT A DETAIL OF THE THERMOSTATIC MIXING VALVE AND
 PIPING ARRANGEMENT TO THE VALVE. COMPLY WITH 2017
 FBC-PLUMBING SEC.607.2.2.
 6) PROVISIONS SHALL BE MADE FOR THERMAL EXPANSION
 CONTROL PER 2017 FBC-PLUMBING SEC.607.3.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW