| 2020-02-24 09:15:35 | 1) A HOT WATER RECIRCULATING LINE IS REQUIRED PER 2017 | | | FBC - PLUMBING SEC. 607.2. | | | 2) SANITARY VENTS EXCEEDING 40 FEET IN DEVELOPED LENGTH | | | SHALL BE INCREASED BY ONE NOMINAL PIPE SIZE FOR THE | | | ENTIRE DEVELOPED LENGTH OF THE VENT PIPE PER 2017 | | | FBC-PLUMBING SE. 906.2. | | | 3) THE SINK BY TOILET ROOM #232 IS LABELED S-3 ON THE | | | SANITARY RISER AND S-1 ON THE WATER RISER. CLARIFY. | | | 4) THE SINK IN THE LAB/PHLEBOTOMY ROOM #227 IS LABELED | | | AS S-1 ON THE SANITARY RISER AND S-2 ON THE WATER | | | RISER. CLARIFY. | | | 5) SUBMIT A DETAIL OF THE THERMOSTATIC MIXING VALVE AND | | | PIPING ARRANGEMENT TO THE VALVE. COMPLY WITH 2017 | | | FBC-PLUMBING SEC.607.2.2. | | | 6) PROVISIONS SHALL BE MADE FOR THERMAL EXPANSION | | | CONTROL PER 2017 FBC-PLUMBING SEC.607.3. | | | | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | PLUMBING PLAN REVIEW | | | 561-805-6692 | | | [email protected] | | | |
|