| 2020-02-24 09:58:57 | 2017 FBC- BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 20020611 |
| | ADD: 1200 S. FLAGLER DR. / SUITE: 1003 |
| | CONT: R & B CONSTRUCTION INC. |
| | TEL: 561-346-8996 |
| | E-MAIL: [email protected] |
| | |
| | 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION. |
| | |
| | 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW |
| | CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES |
| | SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA |
| | BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: MON. FEB. 24/ 2020 |
| | ACTION: DENIED. |
| | |
| | 1) THE COVERSHEET LIST THE MINIMUM BUILDING TYPE AS AN |
| | TYPE II-B CONSTRUCTION. PLEASE NOTE IN AN UNSPRINKLERED |
| | R-2 OCCUPANCY THE BUILDING WOULD BE ALLOWED TO BE 4 |
| | STORIES. IN THE 2017 FBC-B TABLE 404.4 INDICATES THE |
| | BUILDING MUST BE CLASSIFIED AS TYPE I-A CONSTRUCTION. |
| | |
| | 2) WITH THE SUITE # 1003 IT APPEARS IS ON THE 1ST FLOOR |
| | AND IS EXEMPT FROM THE REQUIREMENTS FOR SOUND |
| | INSULATION UNDER THE 2017 WEST PALM BEACH AMENDMENTS TO |
| | THE FLORIDA BUILDING CODE, CHAPTER 1, ADMINISTRATIVE |
| | CODE SECTION 105.2(2). THIS BUILDING IS A HIGH RISE |
| | BUILDING AND STILL MEET THE REQUIREMENT FOUND IN THE |
| | 2017 FBC-B SECTION 603.1. EXCEPTION 2. INSULATION |
| | INSTALLED BETWEEN A FINISHED FLOOR AND SOLID DECKING |
| | WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED TO HAVE A |
| | FLAME SPREAD INDEX OF NOT MORE THAN 200. PLEASE PROVIDE |
| | TO THE CITY THE ACTUAL FLAME SPREAD TEST REPORT. |
| | |
| | 3) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION |
| | & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |
| | JAMES A. WITMER BN, PX,SFP & CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT |