2020-03-25 08:48:39PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC SIXTH EDITION (2017)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) FBC-R314.3.1 ALTERATIONS, REPAIRS AND ADDITIONS.
 WHEN ALTERATIONS, REPAIRS OR ADDITIONS REQUIRING A
 PERMIT OCCUR, OR WHEN ONE OR MORE SLEEPING ROOMS ARE
 ADDED OR CREATED IN EXISTING DWELLINGS, THE INDIVIDUAL
 DWELLING UNIT SHALL BE EQUIPPED WITH SMOKE ALARMS
 LOCATED AS REQUIRED FOR NEW DWELLINGS.
  
 2) FBC 107.3.4 REQUIRES PRODUCT APPROVALS FOR THOSE
 PRODUCTS WHICH ARE REGULATED BY FAC 61G20-3.001 PER
 FLORIDA STATUTE 553.842 (5) TO BE REVIEWED AND APPROVED
 IN WRITING BY THE DESIGNER OF RECORD. THE PRODUCT
 APPROVAL CHECKLIST ON SHEET A-1 DOES NOT LIST NOA NO.
 18-0430.06 FOR SH7700A SINGLE HUNG WINDOWS OR NOA NO.
 17-0614.14 FOR CA-740 CASEMENT WINDOWS. THESE NEED
 DESINER OF RECORD APPROVAL. THE PRODUCT APPROVAL FOR
 THE FL# 239 FOR SH-700 SINGLE HUNG WINDOWS THAT IS
 LISTED IN THE PRODUCT APPROVAL CHECKLIST WAS NOT
 SUBMITTED.
  
 3) THE CEILING OF THE UN-CONDITIONED STORAGE SPACE
 LOCATED BELOW CONDITIONED SPACE IS REQUIRED TO BE
 INSULATED. FBC-EC R402.2.8
  
 4) WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A
 RESPONSE LETTER ADDRESSING EACH ITEM ALONG WITH THE
 CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  
  