| 2020-02-18 04:04:23 | 1) THE PERMIT APPLICATION FOR THE PLUMBING WORK HAS |
| | BEEN SUBMITTED BYA GENERAL CONTRACTOR (CGC). THE |
| | PLUMBING WORK FALLS OUTSIDE THE SCOPE OF A GENERAL |
| | CONTRACTOR'S LICENSE PER FLORIDA STATUTE 489. 105 (3) |
| | (A); 489.113. SUBMIT A PERMIT APPLICATION FROM A DULY |
| | LICENSED PLUMBING CONTRACTOR. |
| | 2) THE PERMIT APPLICATION STATES THAT THE EXISTING TUB |
| | WILL BE CONVERTED TO A NEW SHOWER BUT THE SUBMITTED |
| | PLANS STATES THAT THE TUB IS TO REMAIN. CLARIFY. |
| | ****NOTE: THIS BUILDING WAS BUILT AFTER MARCH 13TH, |
| | 1991 AND THEREFORE BUILT IN COMPLIANCE WITH THE FAIR |
| | HOUSING ACT.THIS UNIT WAS ORIGINALLY DESIGNED AS A |
| | SPECIFICATION "B" UNIT PER THE FAIR HOUSING ACT |
| | GUIDELINES IF THE TUB IN THE MASTER BATH IS CONVERTED |
| | TO A SHOWER, A CLEAR FLOOR SPACE OF 30 INCHES WIDE |
| | MINIMUM BY 48 INCHES LONG MINIMUM MUST BE PROVIDED AT |
| | THE SHOWER STALL, PARALLEL TO THE FIXTURE AND FLUSH |
| | WITH THE CONTROL WALL. THE ONLY FIXTURE THAT IS |
| | PERMITTED TO OVERLAP THE REQUIRED CLEAR FLOOR SPACE FOR |
| | THE SHOWER IS A WALL HUNG LAVATORY AND INSTALLED IN |
| | ACCORDANCE WITH THE FAIR HOUSING ACT GUIDELINES. |
| | 3) CLEARLY INDICATE ON THE PLANS IF THE TUB DRAIN IS |
| | BEING RELOCATED TO ACCOMMODATE THE NEW SHOWER IF INDEED |
| | A NEW SHOWER IS BEING INSTALLED. WPB AMEND. TO FBC SEC. |
| | 107.2.1. |
| | 4) INDICATE ON THE PLANS IF A NEW TUB/SHOWER OR |
| | INDIVIDUAL SHOWER VALVE IS BEING INSTALLED. IF SO, THE |
| | VALVE SHALL COMPLY WITH FBC-PLUMBING SECS.424.3, 424.5. |
| | 5) IF THE OWNER DECIDES TO MOVE FORWARD WITH THE |
| | INSTALLATION OF A SHOWER, THERE IS A BUILDING DIVISION |
| | FORM THAT MUST BE COMPLETED AND SUBMITTED BY THE OWNER |
| | AND DESIGNER/ CONTRACTOR AND BE NOTARIZED REGARDING |
| | COMPLIANCE/NON-COMPLIANCE OF THE FAIR HOUSING ACT. I |
| | HAVE PLACED A BLANK COPY OF THE FORM IN THE PERMIT |
| | APPLICATION FOLDER FOR THE PERUSAL AND USE OF THE |
| | RESPECTIVE PARTIES INVOLVED IN THIS REMODEL, |
| | 6) ADDITIONAL BACKING FOR FUTURE GRAB BARS MAY BE |
| | REQUIRED IN THE WALLS FOR THE NEW SHOWER IN THE MASTER |
| | BATH.COMPLY WITH REQUIREMENT #6 OF THE FAIR HOUSING ACT |
| | AAND SUBMIT AN ELEVATION DRAWING SHOWING THE |
| | REINFORCEMENT AND THE MEASUREMENTS FROM THE FINISH |
| | FLOOR PER THE FHA. REINFORCING FOR GRAB BARS MUST |
| | EXTEND THE FULL WIDTH OF BOTH SIDE WALLS AND THE BACK |
| | WALL. ALSO, SHOW THE WIDTH OF THE REINFORCEMENT. |
| | |
| | |
| | TIM LARGE |
| | CHIEF PLUMBING INSPECTOR |
| | PLUMBING PLAN REVIEW |
| | 561-805-6692 |
| | [email protected] |
| | |