| Plan Review Notes For Permit 20020455 |
| Permit Number |
20020455 |
|
| Review Stop |
B |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2020-05-19 15:11:14 | BUILD OUT | | | REVIEWED BY ROGER MCPHERSON | | | 561-805-6716 | | | [email protected] | | | | | | CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107.2.1 | | | 1) PLEASE SHOW THE FIRE RATING FOR THE ROOM UNDER THE | | | INTERIOR STAIRS TO COMPLY WITH FBC 1011.7.3 --- DRAWING | | | A180.1 STATES SEE DRAWING DETAIL 4/800.1 - - 4/800.1 IS | | | A FIRE RATED WALL DETAIL - - NEED A 1HR FIRE RATED | | | CEILING DETAIL. |
|