| Date |
Text |
| 2020-03-10 15:04:54 | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| | 6TH ED, CHAPTER 1. |
| | WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL |
| | MANUAL REVISED 2017 |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| | 6TH EDITION |
| | FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION |
| | FBC EX = FLORIDA EXISTING BUILDING CODE 2017 6TH |
| | EDITION |
| | FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION |
| | FAC= FLORIDA ADMINISTRATIVE CODE |
| | FS = FLORIDA STATUTES |
| | |
| | |
| | 1ST REVIEW |
| | PLUMBING COMMENTS: DENIED |
| | 1. RE: A170.1; PER FBC ACC 604.6, FLUSH CONTROLS SHALL |
| | BE HAND OPERATED OR AUTOMATIC. HAND OPERATED FLUSH |
| | CONTROLS SHALL COMPLY WITH 309. FLUSH CONTROLS SHALL BE |
| | LOCATED ON THE OPEN SIDE OF THE WATER CLOSET. |
| | 2. RE: A150.1; PER FBC ACC 212.3, WHERE SINKS ARE |
| | PROVIDED, AT LEAST 5 PERCENT, BUT NO FEWER THAN ONE, OF |
| | EACH TYPE PROVIDED IN EACH ACCESSIBLE ROOM OR SPACE |
| | SHALL COMPLY WITH 606. PROVIDE COMPLIANCE FOR ONE SINK |
| | IN THE MODEL ROOM AND THE BREAK ROOM SINK. PROVIDE |
| | CLEAR FLOOR SPACES FOR THE SAME; COMPLY WITH FBC ACC |
| | 305.3 AND 305.5. |
| | 3. PER WPB FBC 107.2.1, INDICATE IF WATER HEATER IS NEW |
| | OR EXISTING. PROVIDE SPECIFICATION/SCHEDULE FOR WATER |
| | HEATER TO INCLUDE STORAGE CAPACITY, ENERGY EFFICIENCY |
| | AND ELECTRICAL CHARACTERISTICS. PROVIDE DETAIL OF WATER |
| | HEATER SHOWING HEATER W/STORAGE CAPACITY, PIPING |
| | INCLUDING CW, HW, VALVES (INCLUDING VACUUM RELIEF VALVE |
| | IF APPLICABLE FBC PL 504.2) , THERMAL EXPANSION CONTROL |
| | DEVICE (INCLUDING SIZE), T&P DISCHARGE (INCLUDING |
| | TERMINATION) AND WATER HEATER PAN AND DRAIN (INCLUDING |
| | TERMINATION); COMPLY WITH FBC PL 607.3, 503.1, 504.1, |
| | 504.4, 504.4.1, 504.5, 504.6, 504.7, 504.7.1 AND |
| | 504.7.2. ADDITIONALLY, AS IT SEEMS TO BE INSTALLED |
| | OVERHEAD, PROVIDE DETAIL OF SUPPORT SYSTEM INCLUDING |
| | ANCHORS. PROVIDE CLEARANCE AND ACCESS FOR MAINTENANCE |
| | AND REPLACEMENT AS DESCRIBED IN FBC PL 502.5. |
| | 4. PER WPB FBC 107.2.1, INDICATE IF RECIRCULATING PUMP |
| | IS NEW OR EXISTING. PROVIDE SPECIFICATION/SCHEDULE FOR |
| | RECIRCULATING PUMP. INCLUDE ELECTRICAL CHARACTERISTICS |
| | AND FLOW CHARACTERISTICS. PROVIDE A DETAIL SHOWING ALL |
| | VALVES AND CONTROLS; INTEGRATE NEW HOT AND HOT RETURN |
| | INTO EXISTING SYSTEM. SHOW LOCATION ON THE PLAN. |
| | 5. PER WPB FBC 107.2.1, PROVIDE DETAIL SHOWING |
| | INTEGRATION OF NEW COLD WATER TO EXISTING. PROVIDE |
| | SIZING OF EXISTING COLD WATER AT THE POINT OF |
| | CONNECTION. REFER TO FBC PL TABLE 604.3 IN CONJUNCTION |
| | WITH FBC PL APPENDIX E TABLES E103.3(2), E103.3(3) AND |
| | FIGURE E103.3(4). IF EXISTING SERVICE IS NOT ADEQUATE, |
| | THEN UPGRADE WATER SERVICE AND DISTRIBUTION TO |
| | ADEQUATELY SUPPORT ALL PLUMBING FIXTURES |
| | 6. PROVIDE TRAP SEAL PROTECTION FOR FLOOR DRAIN. COMPLY |
| | WITH FBC PL 1002.4.1. |
| | 7. PER WPB FBC 107.2.1, PROVIDE A SLAB REPAIR DETAIL ON |
| | THE PLANS. SHOW THE WIDTH OF THE REPAIR, THE MINIMUM |
| | THICKNESS AND PSI OF THE CONCRETE TO BE REPLACED. SHOW |
| | SIZE, LENGTH, SPACING (ON CENTER), MINIMUM EMBEDMENT |
| | AND ANCHORING/ADHESIVE MATERIAL FOR DOWELS. THE REPAIR |
| | SHALL ALSO INCLUDE TERMITE TREATMENT OF THE SOIL AS |
| | WELL AS THE REQUIRED VAPOR BARRIER OVER WELL COMPACTED |
| | SOIL. A COPY OF THE TERMITE CERTIFICATE SHALL BE ONSITE |
| | FOR FINAL INSPECTION. |
| | |
| | |
| | |
| | END OF COMMENTS. |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| | THE PREVIOUSLY REVIEWED SHEETS.ALL PLANS TO BE SIGNED |
| | AND SEALED BY THE DESIGNER AS REQUIRED BY FAC AND FS. |
| | |
| | |
| | |
| | JERALD SMITH |
| | PLUMBING PLANS EXAMINER |
| | CITY OF WEST PALM BEACH |
| | EMAIL [email protected] |
| | PHONE 561-805-6715 |
| | |
| | 20020455 4912 S DIXIE HWY |