Plan Review Notes
Plan Review Notes For Permit 20020455
Permit Number 20020455
Review Stop P
Sequence Number 1
Notes
Date Text
2020-03-10 15:04:54CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL
 MANUAL REVISED 2017
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION
 FBC EX = FLORIDA EXISTING BUILDING CODE 2017 6TH
 EDITION
 FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
  
 1ST REVIEW
 PLUMBING COMMENTS: DENIED
 1. RE: A170.1; PER FBC ACC 604.6, FLUSH CONTROLS SHALL
 BE HAND OPERATED OR AUTOMATIC. HAND OPERATED FLUSH
 CONTROLS SHALL COMPLY WITH 309. FLUSH CONTROLS SHALL BE
 LOCATED ON THE OPEN SIDE OF THE WATER CLOSET.
 2. RE: A150.1; PER FBC ACC 212.3, WHERE SINKS ARE
 PROVIDED, AT LEAST 5 PERCENT, BUT NO FEWER THAN ONE, OF
 EACH TYPE PROVIDED IN EACH ACCESSIBLE ROOM OR SPACE
 SHALL COMPLY WITH 606. PROVIDE COMPLIANCE FOR ONE SINK
 IN THE MODEL ROOM AND THE BREAK ROOM SINK. PROVIDE
 CLEAR FLOOR SPACES FOR THE SAME; COMPLY WITH FBC ACC
 305.3 AND 305.5.
 3. PER WPB FBC 107.2.1, INDICATE IF WATER HEATER IS NEW
 OR EXISTING. PROVIDE SPECIFICATION/SCHEDULE FOR WATER
 HEATER TO INCLUDE STORAGE CAPACITY, ENERGY EFFICIENCY
 AND ELECTRICAL CHARACTERISTICS. PROVIDE DETAIL OF WATER
 HEATER SHOWING HEATER W/STORAGE CAPACITY, PIPING
 INCLUDING CW, HW, VALVES (INCLUDING VACUUM RELIEF VALVE
 IF APPLICABLE FBC PL 504.2) , THERMAL EXPANSION CONTROL
 DEVICE (INCLUDING SIZE), T&P DISCHARGE (INCLUDING
 TERMINATION) AND WATER HEATER PAN AND DRAIN (INCLUDING
 TERMINATION); COMPLY WITH FBC PL 607.3, 503.1, 504.1,
 504.4, 504.4.1, 504.5, 504.6, 504.7, 504.7.1 AND
 504.7.2. ADDITIONALLY, AS IT SEEMS TO BE INSTALLED
 OVERHEAD, PROVIDE DETAIL OF SUPPORT SYSTEM INCLUDING
 ANCHORS. PROVIDE CLEARANCE AND ACCESS FOR MAINTENANCE
 AND REPLACEMENT AS DESCRIBED IN FBC PL 502.5.
 4. PER WPB FBC 107.2.1, INDICATE IF RECIRCULATING PUMP
 IS NEW OR EXISTING. PROVIDE SPECIFICATION/SCHEDULE FOR
 RECIRCULATING PUMP. INCLUDE ELECTRICAL CHARACTERISTICS
 AND FLOW CHARACTERISTICS. PROVIDE A DETAIL SHOWING ALL
 VALVES AND CONTROLS; INTEGRATE NEW HOT AND HOT RETURN
 INTO EXISTING SYSTEM. SHOW LOCATION ON THE PLAN.
 5. PER WPB FBC 107.2.1, PROVIDE DETAIL SHOWING
 INTEGRATION OF NEW COLD WATER TO EXISTING. PROVIDE
 SIZING OF EXISTING COLD WATER AT THE POINT OF
 CONNECTION. REFER TO FBC PL TABLE 604.3 IN CONJUNCTION
 WITH FBC PL APPENDIX E TABLES E103.3(2), E103.3(3) AND
 FIGURE E103.3(4). IF EXISTING SERVICE IS NOT ADEQUATE,
 THEN UPGRADE WATER SERVICE AND DISTRIBUTION TO
 ADEQUATELY SUPPORT ALL PLUMBING FIXTURES
 6. PROVIDE TRAP SEAL PROTECTION FOR FLOOR DRAIN. COMPLY
 WITH FBC PL 1002.4.1.
 7. PER WPB FBC 107.2.1, PROVIDE A SLAB REPAIR DETAIL ON
 THE PLANS. SHOW THE WIDTH OF THE REPAIR, THE MINIMUM
 THICKNESS AND PSI OF THE CONCRETE TO BE REPLACED. SHOW
 SIZE, LENGTH, SPACING (ON CENTER), MINIMUM EMBEDMENT
 AND ANCHORING/ADHESIVE MATERIAL FOR DOWELS. THE REPAIR
 SHALL ALSO INCLUDE TERMITE TREATMENT OF THE SOIL AS
 WELL AS THE REQUIRED VAPOR BARRIER OVER WELL COMPACTED
 SOIL. A COPY OF THE TERMITE CERTIFICATE SHALL BE ONSITE
 FOR FINAL INSPECTION.
  
  
  
 END OF COMMENTS.
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.ALL PLANS TO BE SIGNED
 AND SEALED BY THE DESIGNER AS REQUIRED BY FAC AND FS.
  
  
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 PHONE 561-805-6715
  
 20020455 4912 S DIXIE HWY


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved