Plan Review Notes
Plan Review Notes For Permit 20020455
Permit Number 20020455
Review Stop M
Sequence Number 1
Notes
Date Text
2020-02-24 09:53:261ST REVIEW FBC-2017 MECHANICAL
 PERMIT #20020455
 2/21/20
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH
 EDITION 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEETS M1 & M2: REFER TO SECTION 809.2 FBC-17
 EXISTING BUILDING CODE AND PROVIDE MINIMUM VENTILATION
 CALCULATIONS FOR ALL ROOMS AND SPACES PER TABLE
 403.3.1.1 FBC-17 MECHANICAL. PROVIDE A SCHEDULE THAT
 INDICATES THE REQUIRED AND PROVIDED CFMS OF OUTDOOR
 AIR.
  
 2) M1 & M2: PROVIDE EXHAUST VENTILATION CALCULATIONS
 FOR ALL ROOMS AND SPACES OF THE DENTAL LAB THAT ARE
 BEING VENTILATED BY THE OARTU AND ERV UNITS- SEE TABLE
 403.1.1.1 AND SECTIONS 502.1 & 502.1.3 FBC M. PLEASE
 NOTE THAT RECIRCULATION OF FROM THESE ROOMS AND SPACES
 TO THE OFFICE, BREAKROOM, AND SHIPPING-RECEIVING IS
 LIMITED PER FOOTNOTE G:
 MECHANICAL EXHAUST IS REQUIRED AND RECIRCULATION FROM
 SUCH SPACES IS PROHIBITED EXCEPT THAT RECIRCULATION
 SHALL BE PERMITTED WHERE THE RESULTING SUPPLY AIRSTREAM
 CONSISTS OF NOT MORE THAN 10 PERCENT AIR RECIRCULATED
 FROM THESE SPACES. RECIRCULATION OF AIR THAT IS
 CONTAINED COMPLETELY WITHIN SUCH SPACES SHALL NOT BE
 PROHIBITED (SEE SECTION 403.2.1, ITEMS 2 AND 4).
  
 2A) REFER TO SECTION 510.1 FBC M: BASED ON THE CODE
 SECTION PLEASE PROVIDE A NARRATIVE DESCRIPTION OF THE
 PROCESSES THAT WILL OCCUR IN THE DENTAL LAB INCLUDING
 THE TYPES AND QUANTITIES OF CHEMICALS AND/OR MATERIALS
 THAT WILL USED AND STORED IN THE FACILITY.
  
 3) M1 & M2: PROVIDE SIZING CALCULATIONS FOR THE DUAL
 ZONE ACCU-2 SYSTEM IN THE EQUIPMENT/COMPRESSOR ROOM-
 SECTION 312.1 FBC M.
  
 4) M1 & A160.1: PROVIDE EQUIPMENT SCHEDULES FOR THE
 DENTAL LAB AND EQUIPMENT/COMPRESSOR ROOM. PLEASE
 INCLUDE SUBMITTALS FOR ALL MANUFACTURED EQUIPMENT AND
 APPLIANCES WITH APPROVAL STAMPS BY THE EOR.
  
 5) PROVIDE A COMPRESSED AIR PIPING PLAN: SHOW PIPING
 RUNS, TYPES AND SIZES OF PIPING, AND SUPPORT AND
 HANGING DETAILS- SECTION 107.2.1 WPB.
  
 6) M1: PROVIDE EXHAUST VENTILATION CALCULATIONS FOR THE
 EQUIPMENT/COMPRESSOR ROOM AND A SEQUENCE OF OPERATION
 FOR EF-2- SECTION 502.1 FBC M.
  
 7) M1: THE RETURN AIR TRANSFER FROM THE OFFICE TO THE
 CORRIDOR BY THE STAIRS IS NOT ALLOWED PER SECTION 601.2
 FBC M. PLEASE PROVIDE A COMPLIANT MEANS OF RETURNING
 THE AIR TO AHU-1.
  
 8) M1: PLEASE CLARIFY HOW THE SHADE OFFICE IS BEING
 VENTILATED- SECTION 402 FBC M. PLEASE NOTE THAT
 INTERIOR EXIT STAIRWAYS SHALL BE VENTILATED
 INDEPENDENTLY, AND PENETRATIONS BY DUCTS ARE
 PROHIBITED- SECTION
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD
 SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER
 SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN
 THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS
 PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS
 PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR
 UPDATED.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  
  
  
  
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved