| Date |
Text |
| 2020-02-24 09:53:26 | 1ST REVIEW FBC-2017 MECHANICAL |
| | PERMIT #20020455 |
| | 2/21/20 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| | 2017 |
| | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH |
| | EDITION 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) SHEETS M1 & M2: REFER TO SECTION 809.2 FBC-17 |
| | EXISTING BUILDING CODE AND PROVIDE MINIMUM VENTILATION |
| | CALCULATIONS FOR ALL ROOMS AND SPACES PER TABLE |
| | 403.3.1.1 FBC-17 MECHANICAL. PROVIDE A SCHEDULE THAT |
| | INDICATES THE REQUIRED AND PROVIDED CFMS OF OUTDOOR |
| | AIR. |
| | |
| | 2) M1 & M2: PROVIDE EXHAUST VENTILATION CALCULATIONS |
| | FOR ALL ROOMS AND SPACES OF THE DENTAL LAB THAT ARE |
| | BEING VENTILATED BY THE OARTU AND ERV UNITS- SEE TABLE |
| | 403.1.1.1 AND SECTIONS 502.1 & 502.1.3 FBC M. PLEASE |
| | NOTE THAT RECIRCULATION OF FROM THESE ROOMS AND SPACES |
| | TO THE OFFICE, BREAKROOM, AND SHIPPING-RECEIVING IS |
| | LIMITED PER FOOTNOTE G: |
| | MECHANICAL EXHAUST IS REQUIRED AND RECIRCULATION FROM |
| | SUCH SPACES IS PROHIBITED EXCEPT THAT RECIRCULATION |
| | SHALL BE PERMITTED WHERE THE RESULTING SUPPLY AIRSTREAM |
| | CONSISTS OF NOT MORE THAN 10 PERCENT AIR RECIRCULATED |
| | FROM THESE SPACES. RECIRCULATION OF AIR THAT IS |
| | CONTAINED COMPLETELY WITHIN SUCH SPACES SHALL NOT BE |
| | PROHIBITED (SEE SECTION 403.2.1, ITEMS 2 AND 4). |
| | |
| | 2A) REFER TO SECTION 510.1 FBC M: BASED ON THE CODE |
| | SECTION PLEASE PROVIDE A NARRATIVE DESCRIPTION OF THE |
| | PROCESSES THAT WILL OCCUR IN THE DENTAL LAB INCLUDING |
| | THE TYPES AND QUANTITIES OF CHEMICALS AND/OR MATERIALS |
| | THAT WILL USED AND STORED IN THE FACILITY. |
| | |
| | 3) M1 & M2: PROVIDE SIZING CALCULATIONS FOR THE DUAL |
| | ZONE ACCU-2 SYSTEM IN THE EQUIPMENT/COMPRESSOR ROOM- |
| | SECTION 312.1 FBC M. |
| | |
| | 4) M1 & A160.1: PROVIDE EQUIPMENT SCHEDULES FOR THE |
| | DENTAL LAB AND EQUIPMENT/COMPRESSOR ROOM. PLEASE |
| | INCLUDE SUBMITTALS FOR ALL MANUFACTURED EQUIPMENT AND |
| | APPLIANCES WITH APPROVAL STAMPS BY THE EOR. |
| | |
| | 5) PROVIDE A COMPRESSED AIR PIPING PLAN: SHOW PIPING |
| | RUNS, TYPES AND SIZES OF PIPING, AND SUPPORT AND |
| | HANGING DETAILS- SECTION 107.2.1 WPB. |
| | |
| | 6) M1: PROVIDE EXHAUST VENTILATION CALCULATIONS FOR THE |
| | EQUIPMENT/COMPRESSOR ROOM AND A SEQUENCE OF OPERATION |
| | FOR EF-2- SECTION 502.1 FBC M. |
| | |
| | 7) M1: THE RETURN AIR TRANSFER FROM THE OFFICE TO THE |
| | CORRIDOR BY THE STAIRS IS NOT ALLOWED PER SECTION 601.2 |
| | FBC M. PLEASE PROVIDE A COMPLIANT MEANS OF RETURNING |
| | THE AIR TO AHU-1. |
| | |
| | 8) M1: PLEASE CLARIFY HOW THE SHADE OFFICE IS BEING |
| | VENTILATED- SECTION 402 FBC M. PLEASE NOTE THAT |
| | INTERIOR EXIT STAIRWAYS SHALL BE VENTILATED |
| | INDEPENDENTLY, AND PENETRATIONS BY DUCTS ARE |
| | PROHIBITED- SECTION |
| | |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD |
| | SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER |
| | SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN |
| | THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS |
| | PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS |
| | PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR |
| | UPDATED. |
| | |
| | CHRISTOPHER L. COLE |
| | MECHANICAL PLANS EXAMINER |
| | 401 CLEMATIS STREET |
| | WEST PALM BEACH FL 33401 |
| | 561-805-6719 |
| | [email protected] |
| | |
| | |
| | |
| | |
| | |
| | |